Plan Review Notes
Plan Review Notes For Permit 02021213
Permit Number 02021213
Review Stop B
Sequence Number 1
Notes
Date Text
2002-03-21 00:00:00*********PROVISO*********
 ****TRUSS ENGINEERING****
  
 REVIEWED UNDER:1997 STANDARD BUILDING
 CODE
  
 1) ARCH SPECIFIES SEMCO, NO LONGER IN
 BUSINESS, ENGINEER SPECIFIES BUCKETS
 MANUFACTURED BY HUGHES WHICH ALSO IS
 OUT OF BUSINESS.BOTH CORPS. WERE BOUGHT
 BY USP AND SHOULD USE THE CURRENT PRO-
 DUCT INFORMATION.
  
 2) ARCH. ANCHOR SCHEDULE INDICATES THE
 USE OF (2) STRAPS ON THE SAME TRUSS OR
 GIRDER WITHIN 8" OF EACH OTHER (CMU OR
 CONCRETE EMBEDDMENT OF 4"). IN COMMUNICA
 TING WITH USP ENGINEERS YOU CAN NOT JUST
 DOUBLE THE LOAD WHEN MULTIPLE STRAPS
 ARE LOCATED WITH 8" OF EACH OTHER A DE-
 RATING FACTOR SHALL OCCUR ON AN INDIVID-
 UAL CASE BASES.
  
 LOT #11
 #3 H-7 H-7 1546 LSB UPLIFT, (2) TAPR
 STRAPS REQUIRED, DERAING
 #4 F-3 POINT 1 1675 LBS NOT 1350,
 POINT 8 2030 LBS NOT 1800.
 #5 HG-4 POINT 13ARCH PLANS INDICATE 3250
 AT POINT # 4, 2 SEMCO TAPR22 WHILE A
 3 MEMBER GIRDER REQUIRING A BUCKET WITH
 THE CAPABILITY TO RESIST 2739 UPLIFT
 AND 4678 REACTION.
  
 LOT #12
 #6 H-1 ARCH SHEET 7 INDICATES 2 POINT
 BEARING, TRUSS ENG INDICATES 3 POINT
 BEARING. POINT 11 WILL BE AT 2 HR TOWN-
 HOUSE WALL REQUIRING A BUCKET. NEW 3RD
 POINT BEARING (18) 3579 LBS UPLIFT &
 6145 LBS REACTION.
 #7 HG-2 ANCHOR VALUE AT POINT 1 TO LOW,
 SEE ARCH #4, 2 TAPR222 1485X 2=2970
 DERATING REQUIRED ACTUAL UPLIFT 2898
 #8 H-12 ARCH INDICATES FOR POINT #1 2800
 UPLIFT WHILE TRUSSENG INDICATES 3037
 2 STRAPS 2800 DERATING REQUIRED CLOSER
 THAN 8".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X8412
 BUILDING PROVISO