2002-03-01 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) UNTIL MARCH 1, 2002 EITHER STANDARD |
| BUILDING CODE 1997 OR FLORIDA BUILDING |
| CODE 2001 MAY BE USED.NEITHER CODE IS |
| REFERENCED ON THE PLANS.STATE WHICH |
| CODE THE WORK IS TO BE CONSTRUCTED TO. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) FBC 1012.1.4SECOND FLOOR EXIT DOOR |
| 201/2.THE SWING OF THE RELOCATED DOOR |
| OBSTRUCTS THE ROUTE TO THE STAIRS. |
| MOVE/RECONFIGURE THE DOOR TO AVOID |
| OBSTRUCTION OF THE MEANS OF EGRESS. |
| |
| 4) FBC 2405.2THE GLAZING IN DOOR 201-1 |
| IS IN A 'HAZARDOUS LOCATION' AND IS |
| REQUIRED TO BE SAFETY GLASS SATISFYING |
| THE REQUIREMENTS OF THE CONSUMER |
| PRODUCT SAFETY COMMISSION 16, CODE OF |
| FEDERAL REGULATIONS, PART 1201 |
| (CPSC 16-CFR, PART 1201).SUBMIT |
| DETAILS TO DEMONSTRATE COMPLIANCE. |
| |
| 5) FBC* 104.2.1.2SHEET A1.2, DETAIL 5 |
| AND DOOR ELEVATIONS.STATE THE |
| THICKNESS OF THE TEMPERED GLASS IN THE |
| DOOR AND STOREFRONT.ALSO, AMEND THE |
| FLOOR PLAN TO CLARIFY THE LOCATION OF |
| DOOR ELEVATION D. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |