Plan Review Notes For Permit 02021137 |
Permit Number |
02021137 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-05-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 2) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 3) | | FBC-2001 SEC 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | PLEASE PROVIDE DETAIL NOT SHOWN ON CUT | | SHEET SUBMITTED. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|