2002-03-03 00:00:00 | PLUMBING PLAN REVIEW, FBC 2001,DENIED. |
| (1)GENERAL NOTES #1,THE CURRENT CODE |
| IS,FBC 2001 SEC 424.2.6. ENGINEERING |
| DESIGN. NOT SBCCI 94 PBC SWIMMING POOL. |
| (2) SWIMMING POOL DRAWING IS NOT ACCEPT- |
| ABLE, COMPLY WITH FBC 2001 BUILDING,DRAW |
| INGS AND SPECIFICATIONS,SEC 104.2 |
| SUFFICENT CLARITY AND DETAIL TO INDICATE |
| THE NATURE AND CHARACTER OF WORK. |
| (3) SEC 424.2.6.6. ENTRAPMENT PROTECTION |
| FOR SUCTION INLETS, PROVIDE DETAIL, FOR |
| MAIN DRAIN AND VACUM CLEANING FITTING. |
| (4) SEC 424.2.7.2 PROVIDE DETAILS OF |
| MOUNTING AND ANCHORING POOL EQUIPMENT. |
| (5) SEC 424.2.9 WATER SUPPLY AND LOCAL |
| ORDINANCE,32853-95 BACK FLOW PREVENTER |
| REQUIRED ON WATER SERVICE. |
| (6) ESC 424.2.13.2 JOINTS, CONNECTIONS. |
| PURPLE PRIMER REQUIRED ON PVC PIPING, |
| FBC 2001 PLUMBING, SEC 605.21 |
| (7) SEC 424.2.14.2 WATER RETENTION. |
| PROVIDE A DETAIL OF A POSITIVE MEANS OF |
| RETAINING WATER IN THE POOL HEATER WITH |
| A BY-PASS. |
| (8) SEC 424.2.145 GAS PIPING, SEPERATE |
| PLANS AND PERMIT REQUIRED. |
| END OF COMMENTSPAUL SCHMITZ |