Plan Review Notes
Plan Review Notes For Permit 02021137
Permit Number 02021137
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-03 00:00:00PLUMBING PLAN REVIEW, FBC 2001,DENIED.
 (1)GENERAL NOTES #1,THE CURRENT CODE
 IS,FBC 2001 SEC 424.2.6. ENGINEERING
 DESIGN. NOT SBCCI 94 PBC SWIMMING POOL.
 (2) SWIMMING POOL DRAWING IS NOT ACCEPT-
 ABLE, COMPLY WITH FBC 2001 BUILDING,DRAW
 INGS AND SPECIFICATIONS,SEC 104.2
 SUFFICENT CLARITY AND DETAIL TO INDICATE
 THE NATURE AND CHARACTER OF WORK.
 (3) SEC 424.2.6.6. ENTRAPMENT PROTECTION
 FOR SUCTION INLETS, PROVIDE DETAIL, FOR
 MAIN DRAIN AND VACUM CLEANING FITTING.
 (4) SEC 424.2.7.2 PROVIDE DETAILS OF
 MOUNTING AND ANCHORING POOL EQUIPMENT.
 (5) SEC 424.2.9 WATER SUPPLY AND LOCAL
 ORDINANCE,32853-95 BACK FLOW PREVENTER
 REQUIRED ON WATER SERVICE.
 (6) ESC 424.2.13.2 JOINTS, CONNECTIONS.
 PURPLE PRIMER REQUIRED ON PVC PIPING,
 FBC 2001 PLUMBING, SEC 605.21
 (7) SEC 424.2.14.2 WATER RETENTION.
 PROVIDE A DETAIL OF A POSITIVE MEANS OF
 RETAINING WATER IN THE POOL HEATER WITH
 A BY-PASS.
 (8) SEC 424.2.145 GAS PIPING, SEPERATE
 PLANS AND PERMIT REQUIRED.
 END OF COMMENTSPAUL SCHMITZ
 QUESTIONS561-659-8096X8233