Plan Review Notes For Permit 02021097 |
Permit Number |
02021097 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-05-04 00:00:00 | DENIED | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | FORMATION REQUIRED FOR PLAN REVIEW | | 2) | | FBC-2001 SEC 424.2.6.6.2 SHOW COMPLIANCE | | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL | | NUMBER AND MANUF INFO FOR VAC LOCK. | | (GIVE DETAIL OR ADD NOTE)(SUBMITTAL) | | 3) | | FBC-2001 SEC 424.2.7.1 POOL CIRCULATING | | PUMPS SHALL BE EQUIPPED ON THE INLET | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | STRAINER WHEN USED WITH A PRESSURE FIL- | | TER. (DETAIL) | | 4) | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON | | WATER SERVICE. (ADD TO NOTES) | | 5) | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 6) | | FBC-2001 SEC 424.2.13.2JOINTS AND CON- | | NECTIONS, FBC PLMG SEC 605.21, PURPLE | | PRIMER REQUIRED ON PVC PIPING. (ADD TO | | NOTES) | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|