Plan Review Notes For Permit 02021097 |
Permit Number |
02021097 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-03 00:00:00 | PLUMBING PLAN REVIEW,FBC 2001, DENIED. | | (1) GENERAL NOTES #8 PALM BCH CNTY 1994 | | SWIMMING POOL CODE,CURRENT CODE,FBC 2001 | | SEC 424.2.6 ENGINEERING DESIGN. | | (2) SEC 424.2.6.6.2 SUCTION FITTINGS. | | CLEANING LINE.PROVIDE DETAIL | | (3) SEC 424.2.7.2 PROVIDE A DETAIL OF | | MOUNTING & ANCHORING POOL EQUIPMENT. | | (4) SEC 424.WATER SUPPLY.AND LOCAL | | ORDINANCE #2853-95. BACK FLOW PREVENTER | | REQUIRED ON WATER SERVICE. | | (5) SEC 424.2.21.4 PROVIDE A DETAIL OF | | HYDROSTATIC RELIEF VALVE, AS REQUIRED. | | FOR AREAS OF HIGH WATER TABEL. | | END OF COMMENTS PAUL SCHMITZ | | QUESTIONS561-659-8096X8233 |
|