Plan Review Notes
Plan Review Notes For Permit 02020876
Permit Number 02020876
Review Stop P
Sequence Number 1
Notes
Date Text
2002-03-03 00:00:00PLUMBING PLAN REVIEW,FBC 2001,DENIED
 (1) SEC 424.2.7.2 MOUNTING EQUIPMENT ,
 PROVIDE A DETAIL OF SLAB MEANS OF ANCHOR
 ING EQUIPMENT.
 (2) SEC 424.2.9 AUTO FILL PROVIDE DETAIL
 LOCAL ORDINANCE #2853-95 BACK FLOW
 PREVENTER ON WATER SERVICE.
 (3) SEC 424.2.13.2 JOINTS,CONNECTIONS.
 FBC 2001 PLUMBING SEC 605.21 PURPLE
 PRIMER REQUIRED ON PVC PIPING.
 (4) SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A DETAIL SHOWING A POSITIVE
 MEANS OF RETANING WATER IN THE HEATER,
 WITH BY-PASS.
 (5) SEC 424.2.15 GAS PIPING,SEPERATE
 PLANS AND PERMIT REQUIRED.
 END OF COMMENTS PAUL SCHMITZ