Date |
Text |
2002-03-07 00:00:00 | PERMIT 02020845 |
| ADDRESS: 425 17TH ST |
| COMPLETE PROPRTY MANAGEMENT |
| TEL: (561) 626-2778 |
| |
| |
| 1)- PLANS DO NOT IDENTIFY AS TO WHICH |
| CODE THE PLANS WERE DESIGNED TOO? |
| 1997 SBC OR 2001 FLORIDA CODE? |
| 1997 SBC OR 2001 FLORIDA CODE? |
| 2)- THE PLANS LOOK LIKE THIS IS A 8 UNIT |
| APT. COMPLEX, THE PLAN DOES NOT INDICATE |
| BATHROOMS IN EACH UNIT. |
| PLANS ARE TO BE DRAWN TO A DRAFTSMAN |
| QUALITY WITH A MINIMUM OF 1/8" SCALE. |
| 3)- PLANS DO NOT INDICATE THE BUCK |
| ATACHMENT FOR WINDOWS OR DOOR. |
| 4)- EXTERIOR ENTRY DOORS TO BE RATED |
| AS A 20 MIN. DOOR. |
| 5)-SBC1005.4.4. EMERGENCY ESCAPE & RES- |
| CUE OPENINGS (WINDOWS) GIVE THE CLEAR |
| OPEN AREA FIRST & SECOND FLOOR. |
| 6)- FL ENERGY CODE 101.4.1 PREVIOSLY |
| UNCONDITIONED EXISTING BUILDINGS WHICH |
| WERE PERMITTED PRIOR TO MARCH 15, 1979 |
| TO WHICH HEATING OR COOLING SYSTEMS ARE |
| ADDED SHALL MEET THE PRESCRIPTIVE |
| REQUIREMENTS OF METHOD "C" FORM 600C-97 |
| IF DESIGNED UNDER 97 SBC OR FORM 600C-01 |
| IF DESIGNED UNDER THE 2001 FLORIDA CODE. |
| A FORM SHALL BE REQUIRED FOR THE WORST |
| CASE FIRST FLOOR & SECOND FLOOR. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561) 659-8096 X 8412 |