2002-05-03 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| SBC = STANDARD BUILDING CODE 1997 |
| SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEWS OF 3/7/02 AND 4/15/02: |
| |
| 3) FBC 424.2.17 BARRIER TO SWIMMING POOL |
| THIS COMMENT HAS NOT BEEN PROPERLY |
| ADDRESSED.THE PLANS DO NOT HAVE |
| SUFFICIENT NOTES/DETAILS TO DEMONSTRATE |
| COMPLIANCE WITH FBC 424.2.17.1 THRO' 14. |
| NOTE THAT THE USE OF 'WHITE-OUT' ON |
| PLANS FOR PERMITTING IS INAPPROPRIATE. |
| SUBMIT PLANS THAT DEMONSTRATE COMPLIANCE |
| |
| 7) SBC* 1606.4.2PRODUCT APPROVALS. |
| THIS COMMENT HAS NOT BEEN ADDRESSED. |
| SUBMIT PRODUCT APPROVAL NOTICE(S) OF |
| ACCEPTANCE FOR THE NEW WINDOWS W101, |
| W107, W108 AND W201, AND NEW DOORS D101, |
| D103, D105, D108 AND D204.ALSO, NOTE |
| THAT THE EAST ELEVATION IS STILL |
| REFERING TO D205 WHICH SHOULD BE D204. |
| |
| 8) SBC* 1606.4.2PRODUCT APPROVALS FOR |
| 'CUSTOM DOORS AND WINDOWS'. THIS COMMENT |
| HAS NOT BEEN PROPERLY ADDRESSED.THE |
| COPIES OF THE PRODUCT APPROVAL SUBMITTAL |
| FORMS, THAT HAVE BEEN SIGNED BY THE |
| ENGINEER OF RECORD, ARE NOW MISSING |
| ANSWERS TO QUESTIONS 1.0(F) AND 9.1 |
| |
| 11) SBC* 2308EXTERIOR STUD WALL.THIS |
| COMMENT HAS NOT BEEN PROPERLY ADDRESSED. |
| DETAIL 8/A4.00 SHALL BE AMENDED (OR A |
| DETAIL ADDED) TO SHOW THE ATTACHMENT OF |
| THE NEW STUD WALL TO THE EXISTING WALL, |
| THE WORST CASE BEING IF THE POINT OF |
| ABUTTMENT DOES NOT COINCIDE WITH AN |
| EXISTING STUD LOCATION. |
| |
| |
| NOTE: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES |
| STATES THAT A LOCAL GOVERNMENT SHALL |
| IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| PLAN REVIEW, IF PLANS ARE REJECTED THREE |
| OR MORE TIMES FOR REPEATED FAILURE TO |
| CORRECT A CODE VIOLATION. |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |