Plan Review Notes For Permit 02020826 |
Permit Number |
02020826 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-28 00:00:00 | **************** UNSAT ************** | | | | 1) NOTE: SMOKE DETECTORS ARE REQUIRED | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | PER NFPA-72 2-2.1.1.1. | | PLEASE NOTE THAT SD`S WILL BE REQ`D TO | | BE ADDED TO EXISTING BEDROOMS UPSTAIRS. | | | | 2)NOTE: PLEASE NOTE MISSING GARAGE GFI | | PER 210-52G/210-8 | | | | 3)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS | | EXIST A/C AND NEW AHU& CU-2. PLEASE | | NOTE PLAN SHOWS NEW CU-1. PLEASE CLARIFY | | | | 4)NOTE: PLEASE CLARIFY METER LOCATION, | | E1.00 SHOWS METER AT MAIN HOUSE AND | | RISER DIAGRAM SHOWS AT DETACHED "GUEST" | | HOUSE? | | | | 5)NOTE: PLEASE NOTE MISSING GFI OUTLET | | FOR A/C CU`S. PER 309.2 MECH CODE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | 561-659-8096 EXT 8372 |
|