2002-02-28 00:00:00**************** UNSAT **************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE THAT SD`S WILL BE REQ`D TO
 BE ADDED TO EXISTING BEDROOMS UPSTAIRS.
  
 2)NOTE: PLEASE NOTE MISSING GARAGE GFI
 PER 210-52G/210-8
  
 3)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS
 EXIST A/C AND NEW AHU& CU-2. PLEASE
 NOTE PLAN SHOWS NEW CU-1. PLEASE CLARIFY
  
 4)NOTE: PLEASE CLARIFY METER LOCATION,
 E1.00 SHOWS METER AT MAIN HOUSE AND
 RISER DIAGRAM SHOWS AT DETACHED "GUEST"
 HOUSE?
  
 5)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR A/C CU`S. PER 309.2 MECH CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.