Plan Review Notes
Plan Review Notes For Permit 02020792
Permit Number 02020792
Review Stop M
Sequence Number 1
Notes
Date Text
2002-02-21 00:00:00 
 PROVISO:
  
 PLEASE NOTE, ACCESS OPENING SHALL BE A
 MINIMUM OF 22" X 36" CONTINUOUS FROM THE
 OPENING TO THE EQUIPMENT & ITS CONTROLS.
  
 HAVE AN ACCESSIBLE DISCONNECT.
  
 HAVE A 110-120 VOLT A/C GROUNDING TYPE
 CONVENIENCE OUTLET, CONVENIENT TO
 EQUIPMENT.
  
 A LIGHT LOCATED ON THE SERVICE SIDE
 CONTROLLED BY A SWITCH AT THE ACCESS
 OPENING.