Date |
Text |
2002-03-21 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| UNTIL MARCH 1, 2002 EITHER STANDARD |
| BUILDING CODE 1997 OR FLORIDA BUILDING |
| CODE 2001 MAY BE USED. BECAUSE THE PLANS |
| REFER TO "STANDARD BUILDING CODE AS |
| ADOPTED BY THE CITY", THEY HAVE BEEN |
| REVIEWED FOR COMPLIANCE WITH STANDARD |
| BUILDING CODE 1997. |
| |
| SBC = STANDARD BUILDING CODE 1997 |
| SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SBC* 1606.4SUBMIT PRODUCT APPROVALS |
| FOR THE MULLIONS AND TRANSOMS TO BE USED |
| IN WINDOWS INCORPORATING MULTIPLE WINDOW |
| UNITS.ALSO, THE SUBMITTED NOTICE OF |
| ACCEPTANCE (NO. 99-1110.04) FOR THE |
| SERIES 6000 ALUMINUM FIXED WINDOW IS |
| MISSING DRAWING SHEET 2 OF 4. |
| |
| 4) SBC* 1606.4STATE THE REQUIREMENT |
| FOR INSTALLATION OF HURRICANE PROTECTION |
| SHUTTERS ON THE PLANS. |
| |
| 5) SBC 1507.1.2ROOF TILE PRODUCT |
| APPROVAL.THE NOTICE OF ACCEPTANCE NO |
| AND MANUFACTURER ON SHEET 2 OF THE |
| SUBMITTED PRODUCT APPROVAL DOES NOT |
| CORRESPOND TO THAT OF THE REMAINING |
| SHEETS.REPLACE SHEET 2 OR SUBMIT A |
| COMPLETE AND CONSISTENT PRODUCT APPROVAL |
| |
| 6) SBC 2309.7SHEET A8, TYPICAL WALL |
| SECTION.CROSS VENTILATION SHALL BE |
| PROVIDED FOR EACH SEPARATE ATTIC SPACE. |
| AT LEAST 50% OF THE REQUIRED VENTILATION |
| AREA SHALL BE AT A LEVEL NO LESS THAN |
| 3FT ABOVE THE EAVES VENTS. AMEND THE |
| THE PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 7) SBC* 104.2SHEET A3, FLOOR PLAN. |
| THE MASTER BEDROOM PRIVACY WALL CROSS- |
| SECTION REFERENCE A7/25 SHOULD READ |
| A8/25. |
| |
| 8) SBC* 104.2SHEET A2, FOUNDATION PLAN |
| THICKENED EDGE TE1 AND TE2 ARE NOT SHOWN |
| ON THE FOOTING SCHEDULE.IT SHOULD BE |
| AMENDED TO REFER TO THE TE1 AND TE2 |
| DETAILS ON SHEET A8. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUERIES PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |