Plan Review Notes
Plan Review Notes For Permit 02020712
Permit Number 02020712
Review Stop M
Sequence Number 1
Notes
Date Text
2002-02-20 00:00:00*******************DENIED***************
  
  
 APPLICATION INDICATES TENANT SEPARATION,
 SHOW COMPLIANCE WITH FLA ENERGY CODE
 (1997), THE SUPPLY OF HEATING & COOLING
 TO EACH ZONE SHALL BE CONTROLLED BY
 INDIVIDUAL THERMOSTATIC CONTROLS FOR
 CONTROLLING THE TEMPERATURE WITHIN THE
 ZONE.
  
 INDICATE THE USE OF THE ROOM TO THE
 SOUTHEAST.NO VENTILATION PROVIDED FOR
 THIS SPACE.ELECTIRICAL PLAN INDICATES
 AN OUTLET FOR TELEPHONE & COMPUTER.
  
 PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  