2002-02-22 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) UNTIL MARCH 1, 2002 EITHER STANDARD |
| BUILDING CODE 1997 OR FLORIDA BUILDING |
| CODE 2001 MAY BE USED.NEITHER CODE IS |
| REFERENCED ON THE PLANS.STATE WHICH |
| CODE THE WORK IS TO BE CONSTRUCTED TO. |
| |
| 2) AMEND THE PLANS TO SHOW THE |
| USE/OCCUPANCY OF EACH ROOM. |
| |
| 3) THE PROJECT DESCRIPTION ON THE PERMIT |
| APPLICATION FORM STATES "TENANT |
| SEPARATION WALLS", BUT THE NEW WALLS ON |
| THE PLANS ARE ANNOTATED AS "NEW INTERIOR |
| PARTITION",AND THERE ARE INTERCONNECTING |
| DOORS BETWEEN ROOMS EAST OF THE ELEVATOR |
| ANNOTATE THE PLANS TO CLARIFY THE SCOPE |
| OF THE PERMIT APPLICATION. |
| |
| 4) FBC 1005.4EVERY SLEEPING ROOM SHALL |
| HAVE AT LEAST ONE EXTERIOR EMERGENCY |
| ESCAPE AND RESCUE OPENING.IDENTIFY THE |
| BEDROOMS ON THE PLANS AND DEMONSTRATE |
| COMPLIANCE.THE INTERNAL DOOR HARDWARE |
| SHALL NOT BE LOCKABLE, PREVENTING ACCESS |
| TO THE EXISTING EXIT DOOR. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |