Plan Review Notes
Plan Review Notes For Permit 02020701
Permit Number 02020701
Review Stop E
Sequence Number 2
Notes
Date Text
2002-03-29 00:00:00**************** UNSAT *****************
  
 1}PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} WIRE SIZE LISTED FOR THE SERVICE
 FEEDER IS INCORRECT FOR 200 AMPS.
  
 3} PLAN ONLY SHOWS THE PANEL
 LOCATION,PLEASE SHOW METER AND
 DISCONNECT LOCATION ALSO.
  
 PLEASE PROVIDE INFORMATION REQUESTED AND
 RESUMBIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392