2002-02-21 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE PERMIT APPLICATION
 MENTIONS A NEW UNDERGROUND TO MAIN
 HOUSE BUT NOTHING SHOWN ON ELECTRICAL
 PLANS?? PLEASE CLARIFY GROUPING OF MAINS
 AND NEW? SERVICE FOR MAIN HOUSE.
 SUBMIT ON RISER DIAGRAM.
 PER ZONING REG`S, ONLY ONE METER
 PERMITTED.
  
 3)NOTE: PLEASE NOTE THAT PER 210-8 ALL
 OUTLETS IN GARAGE NEED TO BE SHOWN AS
 GFI/GFI PROTECTED.
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUND BETWEEN MAIN DISCONNECT AND
 PANEL PER 250-122
  
 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER
 STEEL IS REQ`D PER 250-50.
 PLEASE SHOW ON RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  