Plan Review Notes For Permit 02020701 |
Permit Number |
02020701 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-21 00:00:00 | *************** UNSAT **************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2)NOTE: PLEASE NOTE PERMIT APPLICATION | | MENTIONS A NEW UNDERGROUND TO MAIN | | HOUSE BUT NOTHING SHOWN ON ELECTRICAL | | PLANS?? PLEASE CLARIFY GROUPING OF MAINS | | AND NEW? SERVICE FOR MAIN HOUSE. | | SUBMIT ON RISER DIAGRAM. | | PER ZONING REG`S, ONLY ONE METER | | PERMITTED. | | | | 3)NOTE: PLEASE NOTE THAT PER 210-8 ALL | | OUTLETS IN GARAGE NEED TO BE SHOWN AS | | GFI/GFI PROTECTED. | | | | 4)NOTE: PLEASE NOTE MISSING EQUIPMENT | | GROUND BETWEEN MAIN DISCONNECT AND | | PANEL PER 250-122 | | | | 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER | | STEEL IS REQ`D PER 250-50. | | PLEASE SHOW ON RISER. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|