Plan Review Notes For Permit 02020691 |
Permit Number |
02020691 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-01 00:00:00 | *************** UNSAT *************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT. PLEASE NOTE THAT | | MAINS/BRKRS AND PANELS NEED TO BE RATED | | FOR THE AVAILABLE FAULT CURRENT. PER | | 110-9 | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210-8-A-6. | | | | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | GOING TO BUILDING STEEL AND COLD WATER | | PER 250-50. | | MISSING BLDG/FOOTER STEEL. | | | | 5)NOTE: PLEASE SEE 210-12 PLEASE LIST | | THE REQ`D ARC FAULT PROTECTED CIRCUITS | | ON PANEL SCHEDULE. PLEASE NOTE THAT | | THIS REQ`MENT CAME INTO AFFECT JAN 1ST | | 2002 | | | | 6)NOTE: PLEASE NOTE THAT NOTES MENTION | | 99 NEC AND STATE CODE.?? | | PLEASE NOTE THAT THERE IS NO STATE | | ELECTRICAL CODE THAT WE ARE AWARE OF. | | PLEASE CLARIFY. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|