Plan Review Notes
Plan Review Notes For Permit 02020691
Permit Number 02020691
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-01 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT. PLEASE NOTE THAT
 MAINS/BRKRS AND PANELS NEED TO BE RATED
 FOR THE AVAILABLE FAULT CURRENT. PER
 110-9
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 5)NOTE: PLEASE SEE 210-12 PLEASE LIST
 THE REQ`D ARC FAULT PROTECTED CIRCUITS
 ON PANEL SCHEDULE. PLEASE NOTE THAT
 THIS REQ`MENT CAME INTO AFFECT JAN 1ST
 2002
  
 6)NOTE: PLEASE NOTE THAT NOTES MENTION
 99 NEC AND STATE CODE.??
 PLEASE NOTE THAT THERE IS NO STATE
 ELECTRICAL CODE THAT WE ARE AWARE OF.
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372