Plan Review Notes For Permit 02020688 |
Permit Number |
02020688 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-03-01 00:00:00 | **************** UNSAT **************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED PER 210-8-A-6. | | | | 3) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 4)NOTE: PLEASE NOTE MISSING HALL OUTLET | | PER 210-52H IN DOWNSTAIRS HALL. | | | | 5)NOTE: PLEASE CALRIFY NOTE THAT MENTION | | -S 99 NEC AND STATE CODE? PLEASE NOTE | | THAT THERE IS NO STATE ELECTRICAL CODE | | THAT WE ARE AWARE OF. PLEASE CLARIFY | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|