Plan Review Notes
Plan Review Notes For Permit 02020688
Permit Number 02020688
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-01 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52H IN DOWNSTAIRS HALL.
  
 5)NOTE: PLEASE CALRIFY NOTE THAT MENTION
 -S 99 NEC AND STATE CODE? PLEASE NOTE
 THAT THERE IS NO STATE ELECTRICAL CODE
 THAT WE ARE AWARE OF. PLEASE CLARIFY
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372