Plan Review Notes
Plan Review Notes For Permit 02020685
Permit Number 02020685
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-27 00:00:00*******************UNSAT!***************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONAND MAKE THE NECESSARY
 CHANGES ON THE PLAN.
  
 1) PROVIDE AN A.I.C. RATING TO THE FIRST
 MEANS OF DISCONNECT AS PER 110-9 &
 110-10.
  
 2) PLEASE NOTE THAT A.F.C.I.MUST BE
 PROVIDED AS PER 210-12.INDICATE SAME ON
 PANEL SCHEDULE.
  
 3) BATH ROOM CIRCUITS MUST COMPLY WITH
 210-11(C)(3). INDICATE SAME ON PANEL
 SCHEDULE.
  
 4) COMPLY WITH N.F.P.A.-72,2-5.2.1.6(B)
 WHEN INSTALLING THE SMOKE DETECTOR IN
 THE HALL BETWEEN BED ROOMS 2&3.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY 0F WEST PALM BEACH
 561/ 659-8096