Plan Review Notes For Permit 02020685 |
Permit Number |
02020685 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-27 00:00:00 | *******************UNSAT!*************** | | PLEASE PROVIDE THE FOLLOWING | | INFORMATIONAND MAKE THE NECESSARY | | CHANGES ON THE PLAN. | | | | 1) PROVIDE AN A.I.C. RATING TO THE FIRST | | MEANS OF DISCONNECT AS PER 110-9 & | | 110-10. | | | | 2) PLEASE NOTE THAT A.F.C.I.MUST BE | | PROVIDED AS PER 210-12.INDICATE SAME ON | | PANEL SCHEDULE. | | | | 3) BATH ROOM CIRCUITS MUST COMPLY WITH | | 210-11(C)(3). INDICATE SAME ON PANEL | | SCHEDULE. | | | | 4) COMPLY WITH N.F.P.A.-72,2-5.2.1.6(B) | | WHEN INSTALLING THE SMOKE DETECTOR IN | | THE HALL BETWEEN BED ROOMS 2&3. | | | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | CITY 0F WEST PALM BEACH | | 561/ 659-8096 |
|