Plan Review Notes
Plan Review Notes For Permit 02020683
Permit Number 02020683
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-01 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 -ED. PLEASE NOTE MAIN/BRKRS AND PANELS
 ARE TO BE RATED FOR THE AVAILABLE FAULT
 CURRENTPER 110-9.
  
 2) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 4) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 5)NOTE: PLEASE NOTE MISSING HALL OUTLET
 PER 210-52H
  
 6)NOTE: PLEASE NOTE THAT AS OF JAN 1ST,
 2002 NEC. ART 210-12. PLEASE LIST THE
 ARC FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULES.
  
 7)NOTE: PLEASE CLARIFY NOTE THAT MENTION
 -S 99 NEC AND STATE CODE? PLEASE NOTE
 THAT WE ARE UNDER 99 NEC AND OUR LOCAL
 AMENDMENTS BUT THERE IS NO STATE
 ELECTRICAL CODE THAT WE ARE AWARE OF?
 PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372