Plan Review Notes
Plan Review Notes For Permit 02020618
Permit Number 02020618
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-25 00:00:00DENIED
 REFERENCE: FACBC-97 - SPC-94
  
 1) SPC TABLE 407 REQUIRED 1 DRINKING
 FOUNTAIN.
 2) SHT M-1 PLEASE PROVIDE A SANITARY
 RISER DIAGRAM WITH PIPE SIZING, AND SHOW
 TIE IN AND VENT.
 3) SHT M-1 PLEASE PROVIDE A WATER RISER
 DIAGRAM WITH PIPE SIZING AND IF A WATER
 HAMMER ARRESTOR IS USED SHOW LOCATION
 NEAR FIXTURE NOT AT TOP OF DRAP.
 4) PLEASE SHOW DETAIL OF KITCHEN SINK.
 PLEASE SHOW COMPLIANCE WITH FACBC SEC.
 4.24.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377.