2002-02-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 1) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE COPY ROOM DOOR TO THE CORRIDOR IS
 NOT SHOWN AS EXISTING ON THE DEMOLITION
 PLAN.EITHER AMEND THE PLANS TO SHOW
 THAT THIS DOOR IS EXISTING OR SPECIFY A
 NEW ONE-HOUR FIRE-RATED DOOR.
  
 4) THE FIRE REVIEW COMMENT (NO.2) SHALL
 BE ADDRESSED IN RESPECT OF THE PROPOSED
 ONE-HOUR FIRE-RATED ENTRY DOORS WITH
 'FIRE LITE' GLAZING.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499