2002-03-07 00:00:00A) THE REQUIRED FIRE ALARM SYSTEM ARE TO
 BE PERMITTED SEPARATELY. PLANS, CUT
 SHEETS, WIRING DIAGRAMS, AND BATTERY
 CALCULATIONS ARE TO BE PROVIDED. MANUAL
 PULL STATIONS AND HORN STROBES ARE TO
 BE PROVIDED THROUGHOUT THE BUILDING. ON
 3.1.02 WRITER CONTACTED FELIX SIERRA
 WH ADVISED THAT THE FIRE ALARM CONTROL
 PANEL WILL BE LOCATED IN AN EXTERIOR
 STORAGE ROOM. THE FIRE ALARM SYSTEM
 IS TO BE CLASS A OR FULLY ADDRESSABLE.
 B) THE EXIT STAIRS ARE TO BE AT LEAST
 36" WIDE SINCE OCCUPANT LOADS ARE
 EXPECTED TO BE LESS THAN 50 PERSONS.
 THE MINIMUM HEIGHT OF RISER SHALL BE
 4", MAXIMUM HEIGHT OF RISER 7", WITH
 THE MINIMUM TREAD DEPTH OF AT LEAST
 11"S.
 C) ILLUMINATION IS TO BE PROVIDED FOR
 THE MEANS OF EGRESS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497