Plan Review Notes
Plan Review Notes For Permit 02020594
Permit Number 02020594
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-12 00:00:00DENIED
 REFERENCE:FBC-2001 - FHA AMEND-98
 DESIGN MANUAL
  
 1) SHT T1.01 COVER SHEET CALLS FOR
 IRRAGATION SHEETS IR-1/IR-2, NONE
 FOUND.PLEASE SUBMIT IRRIGATION SHEETS.
 2) SHT 10.01 GENERAL NOTES #2 CHANGE
 CODE REFERENCE TO READ FLA. BLDG. CODE
 2001.
 3) SHT P-2 1ST FLOOR/1ST FLOOR (REV),
 "A" CLEANOUT REQUIRED AT CHANGE OF
 DIRECTION GREATER THAN 45 DEGREES. FBC
 SEC 708.3.3.
 4) SHT P-2 2ND FLOOR/2ND FLOOR (REV),
 "A" MINIMUM 1-1/2" WASTE ARM TO KITCHEN
 SINK NOT 1" AS SHOWN. FBC 709.1
 5) SHT P-3 1ST FLOOR/1ST FLOOR (REV),
 "B" CLEANOUT REQUIRED AT CHANGE OF
 DIRECTION GREATER THAN 45 DEGREES. FBC
 SEC 708.3.3.
 6)SHT P-3 2ND FLOOR/2ND FLOOR (REV),
 "B" MINIMUM 1-1/2" WASTE ARM TO
 KITCHEN SINK NOT 1" AS SHOWN. FBC 709.1
 7) SHT P-6 WATER RISER DIAGRAMS TYPICAL
 FOR ALL UNITS. WATER HAMMER ARRESTORS
 SHALL BE LOCATED IN AN "EFFECTIVE
 RANGE" OF ALL QUICK CLOSING VALVES
 (SOLENOID) PLEASE SHOW THESE ON RISER
 DIAGRAMS. FBC SEC 604.9
 8) SHT P-6 WATER RISER DIAGRAM FOR "C"
 UNIT SHOWS AIR CHAMBER. AIR CHAMBERS
 ARE NOT APPROVED, PLEASE REMOVE.
 9) SHT P-6 SANITARY RISER DIAGRAM. W/M
 STACK SHOWS 2" ON HORIZONTAL DRAIN LINE
 BUT 3" ON VERTICAL STACK. PLEASE SIZE
 DRAIN FOR 3" ALSO.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377