2002-02-12 00:00:00 | *******************DENIED*************** |
| |
| 2001 FBC, MECHANICAL |
| |
| 1.SHOW COMPLIANCE WITH FBC CHAPTER 13 |
| SECTION 610.1.ABC.1, ALL AIR |
| DISTRIBUTION SYSTEMS SHALL BE SIZED |
| & DESIGNED IN ACCORDANCE WITH |
| RECOGNIZED ENGINEERING STANDARDS |
| SUCH AS ACCA MANUAL D OR OTHER |
| STANDARDS. |
| |
| 2.REVISE ALL PLAN SHEETS TO REFER TO |
| THE "2001 FLORIDA BUILDING CODE" |
| INSTEAD OF THE 1997 SBC. |
| |
| 3.PLAN SHEET A7.03 DETAIL #1 - |
| AUXILIARY DRAIN PAN WITH OVERFLOW |
| PROTECTION FOR ALL UNITS AS PER 2001 |
| FBC, MECHANICAL 307.2.3. |
| |
| 4.PLAN SHEET M-2 - INDICATE DUCT SIZE |
| OF BATHROOM EXHAUST. |
| |
| 5.PLAN SHEET M-3 - CLARIFY DETAIL OF |
| 1ST FL (REV), EXHAUST DUCT DOES NOT |
| APPEAR TO BE IN A RATED SHAFT. |
| |
| 6.PROVIDE EXHAUST FAN MODEL # & CFM. |
| |
| 7.SHOW COMPLIANCE WITH 2001 FBC, MECH |
| 403.1 & 601.4, BALANCED AIR RETURN. |
| |
| 8.PROVIDE OUTSIDE AIR CALCULATIONS AS |
| PER 403.3 & TABLE 403.3, REQUIRED |
| OUTDOOR VENTILATION AIR FOR PRIVATE |
| DWELLING SINGLE AND MULTIPLE LIVING |
| AREAS. |
| |
| 9.HOLD LANDSCAPE BACK 12" FROM |
| CONDENSER UNITS. |
| |
| 10. CONDENSER UNITS NOT TO PLACED UNDER |
| THE DRIP EDGE OF THE STRUCTURE. |
| |
| 11. CONDENSATE SHALL TERMINATE 12" FROM |
| THE BUILDING STRUCTURE AS PER 2001 |
| FBC 1503.4.4. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT 659-8096 |
| EXT. 8388. |