Plan Review Notes
Plan Review Notes For Permit 02020594
Permit Number 02020594
Review Stop M
Sequence Number 1
Notes
Date Text
2002-02-12 00:00:00*******************DENIED***************
  
 2001 FBC, MECHANICAL
  
 1.SHOW COMPLIANCE WITH FBC CHAPTER 13
 SECTION 610.1.ABC.1, ALL AIR
 DISTRIBUTION SYSTEMS SHALL BE SIZED
 & DESIGNED IN ACCORDANCE WITH
 RECOGNIZED ENGINEERING STANDARDS
 SUCH AS ACCA MANUAL D OR OTHER
 STANDARDS.
  
 2.REVISE ALL PLAN SHEETS TO REFER TO
 THE "2001 FLORIDA BUILDING CODE"
 INSTEAD OF THE 1997 SBC.
  
 3.PLAN SHEET A7.03 DETAIL #1 -
 AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION FOR ALL UNITS AS PER 2001
 FBC, MECHANICAL 307.2.3.
  
 4.PLAN SHEET M-2 - INDICATE DUCT SIZE
 OF BATHROOM EXHAUST.
  
 5.PLAN SHEET M-3 - CLARIFY DETAIL OF
 1ST FL (REV), EXHAUST DUCT DOES NOT
 APPEAR TO BE IN A RATED SHAFT.
  
 6.PROVIDE EXHAUST FAN MODEL # & CFM.
  
 7.SHOW COMPLIANCE WITH 2001 FBC, MECH
 403.1 & 601.4, BALANCED AIR RETURN.
  
 8.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 403.3 & TABLE 403.3, REQUIRED
 OUTDOOR VENTILATION AIR FOR PRIVATE
 DWELLING SINGLE AND MULTIPLE LIVING
 AREAS.
  
 9.HOLD LANDSCAPE BACK 12" FROM
 CONDENSER UNITS.
  
 10. CONDENSER UNITS NOT TO PLACED UNDER
 THE DRIP EDGE OF THE STRUCTURE.
  
 11. CONDENSATE SHALL TERMINATE 12" FROM
 THE BUILDING STRUCTURE AS PER 2001
 FBC 1503.4.4.
  