2002-02-12 00:00:00 | | | THE BUILDING WAS REVIEWED UNDER THE | | FLORIDA FIRE PREVENTION CODE. | | 1) FIRE HYDRANTS WILL BE RELOCATED TO | | ISLANDS TO PREVENT PROBLEMS WITH ACCESS | | TO THEM. THIS ARRANGEMENT WAS AGREED TO | | BY MR. FELIX SIERRA. | | 2) GENERAL NOTES SECTION SHOULD READ | | FLORIDA FIRE PREVENTION CODE. | | 3) ALL STORAGE ROOMS OUTSIDE OF DWELLING | | UNITS TO BE PROTECTED BY AT LEASAT ONE | | HOUR FIRE SEPARATION OF FIRE SPRINKLERS. | | 4) THE REQUIREMENT FOR A FIRE ALARM | | SYSTEM STILL SEEMS TO BE PRESENT. THE | | TWO EXCEPTIONS TO THIS CODE REQUIREMENT | | DOES NOT APPEAR TO APPLY. PLEASE REVIEW | | CODE REQUIREMENT AND EXCEPTIONS. | | 5) THE INFORMATION PROVIDED FOR THE | | WINDOWS IS CONFUSING. ARE THE EGRESS | | WINDOWS, SELF-CLOSING. PLEASE PROVIDE | | ADDITIONAL DETAILS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096, EXT. 8497 | | 835-2910 |
|