Plan Review Notes
Plan Review Notes For Permit 02020594
Permit Number 02020594
Review Stop B
Sequence Number 1
Notes
Date Text
2002-02-12 00:00:00 
 BUILDING:H. PISKURA
  
 FBC 705.1.3, REQUIRES THE FIRE RATED
 WINDOWS, (AND DOORS), TO BE LABELED AND
 LISTED IN ACCORDANCE WITH NFPA 80-95.
  
 THE STORAGE ROOM DOORS SHOWN AS (9) ON
 THE PLAN ARE REQUIRED TO BE RATED [45
 MIN] SINCE THEY ARE WITHIN THE TEN FEET
 WIDE SHADOW OF PROTECTION REQUIRED BY
 FBC 1006.2.4.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved