2002-02-12 00:00:00 | ***************** UNSAT ************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2)NOTE: PLEASE NOTE THAT MAIN DISCONNECT | | IS NOT SHOWN NEXT TO METERCAN. PLEASE | | SHOW. | | | | 3)NOTE: PLEASE NOTE THAT NEW A/C COND. | | UNITS IS NOT SHOWN. DISC PER 440-11 AND | | GFI PER 309.2 MECH CODE | | | | 4)NOTE: PLEASE NOTE THAT EQUIPMENT | | GROUNDING IS MISSING BETWEEN MAIN DISC | | AND PANEL.PER 250-122 | | | | 5)NOTE: PLEASE LOAD FOR WATER HEATER, | | LOAD CALCS SHOW "GAS" AND PANEL SCHEDULE | | SHOW ELECTRICAL.?? | | | | 6) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 7)NOTE: PLEASE CLARIFY DRYER LOAD? | | PANEL SCHEDULE SHOWS 1-POLE 20A AND LOAD | | | | | | 8)NOTE: PLEASE CLARIFY LOAD FOR "NEW" | | AHU. PANEL SCHEDULE SHOWS 60A OCP WITH | | 45A LOAD AND LOAD CALCS SHOW 5KW LOAD?? | | PLEASE CORRELATE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|