Plan Review Notes
Plan Review Notes For Permit 02020454
Permit Number 02020454
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-12 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE THAT MAIN DISCONNECT
 IS NOT SHOWN NEXT TO METERCAN. PLEASE
 SHOW.
  
 3)NOTE: PLEASE NOTE THAT NEW A/C COND.
 UNITS IS NOT SHOWN. DISC PER 440-11 AND
 GFI PER 309.2 MECH CODE
  
 4)NOTE: PLEASE NOTE THAT EQUIPMENT
 GROUNDING IS MISSING BETWEEN MAIN DISC
 AND PANEL.PER 250-122
  
 5)NOTE: PLEASE LOAD FOR WATER HEATER,
 LOAD CALCS SHOW "GAS" AND PANEL SCHEDULE
 SHOW ELECTRICAL.??
  
 6) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 7)NOTE: PLEASE CLARIFY DRYER LOAD?
 PANEL SCHEDULE SHOWS 1-POLE 20A AND LOAD
  
  
 8)NOTE: PLEASE CLARIFY LOAD FOR "NEW"
 AHU. PANEL SCHEDULE SHOWS 60A OCP WITH
 45A LOAD AND LOAD CALCS SHOW 5KW LOAD??
 PLEASE CORRELATE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372