2002-04-11 00:00:00 | DENIED |
| REFERENCE: SPC-94 - FACBC-97 |
| |
| FOR FOUNDATION PERMIT |
| 1) PER PREVIOUS REVIEW: SUBMIT CALCULAT- |
| IONS FOR MINIMUM FACILITIES PER SPC TAB. |
| 407 AND SEC. 407.1.3. CALCULATIONS SUB- |
| MITTED NOT CLEAR. MULTIPLE OCCUPANCY - |
| SHOW MIN. FAC FOR EACH OCCUPANCY. |
| 2) PER PREVIOUS REVIEW: SUBMIT STORM |
| RISER DIAGRAM. INDICATE HOW STORM PIPING |
| WILL BE RUN. WILL IT BE IN SLAB? |
| |
| --FOR BLDG PERMIT-- |
| 3) PLANS SHALL BE ROUTED TO THE PALM |
| BEACH COUNTY HEALTH UNIT, DIVISION OF |
| ENVIRONMENTAL HEALTH. 901 EVERNIA STREET |
| WPB FLA 33401. THIS SHALL BE DONE BEFORE |
| RESUBMITTING FOR PLAN REVIEW. |
| 4) GREASE LINE SHOWS NEW LINE TO MEZZ. |
| THIS NEW LINE SHALL RUN TO SANITARY. |
| 5) HAND SINKS IN KITCHEN DO NOT NEED TO |
| BE INDIRECTLY DRAINED. PREVIOUS COMMENT |
| #6, I DID NOT KNOW THEY WERE HAND SINKS. |
| 6) SHTS P-1/P-2 SANITARY RISER DIAGRAM |
| DOES NOT REFLECT FLOOR PLAN. |
| A) DRINKING FOUNTAINS BY MENS AND WOMEN |
| REST ROOMS NOT ON RISER DIAGRAM. |
| B) ARTS & CRAFTS TAKEN OFF BEFORE MENS |
| ROOM ON FLOOR PLAN BUT NOT ON RISER DIA. |
| C) OFFICE BATH ROOM TAKEN OFF AFTER |
| DRAIN LINE TURNS TO MENS ROOM NOT REFLEC |
| TED ON RISER DIAGRAM. |
| 7) GREASE TRAP SHALL BE SIZED BY RODNEY |
| COMPO, ENVIRONMENTAL COMPLIANCE (561) |
| 837-4074. (SEE ATTACHED SHEET FOR APPRO- |
| VED GREASE TRAP DETAIL) |
| 8) SHOWER BATH BY DANCE CLASS SHALL BE |
| ACCESSIBLE PER FACBC-SEC 4.1.3(11) |
| |