Plan Review Notes For Permit 02020235
Permit Number 02020235
Review Stop P
Sequence Number 2
Notes
Date Text
2002-04-11 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 FOR FOUNDATION PERMIT
 1) PER PREVIOUS REVIEW: SUBMIT CALCULAT-
 IONS FOR MINIMUM FACILITIES PER SPC TAB.
 407 AND SEC. 407.1.3. CALCULATIONS SUB-
 MITTED NOT CLEAR. MULTIPLE OCCUPANCY -
 SHOW MIN. FAC FOR EACH OCCUPANCY.
 2) PER PREVIOUS REVIEW: SUBMIT STORM
 RISER DIAGRAM. INDICATE HOW STORM PIPING
 WILL BE RUN. WILL IT BE IN SLAB?
  
 --FOR BLDG PERMIT--
 3) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT, DIVISION OF
 ENVIRONMENTAL HEALTH. 901 EVERNIA STREET
 WPB FLA 33401. THIS SHALL BE DONE BEFORE
 RESUBMITTING FOR PLAN REVIEW.
 4) GREASE LINE SHOWS NEW LINE TO MEZZ.
 THIS NEW LINE SHALL RUN TO SANITARY.
 5) HAND SINKS IN KITCHEN DO NOT NEED TO
 BE INDIRECTLY DRAINED. PREVIOUS COMMENT
 #6, I DID NOT KNOW THEY WERE HAND SINKS.
 6) SHTS P-1/P-2 SANITARY RISER DIAGRAM
 DOES NOT REFLECT FLOOR PLAN.
 A) DRINKING FOUNTAINS BY MENS AND WOMEN
 REST ROOMS NOT ON RISER DIAGRAM.
 B) ARTS & CRAFTS TAKEN OFF BEFORE MENS
 ROOM ON FLOOR PLAN BUT NOT ON RISER DIA.
 C) OFFICE BATH ROOM TAKEN OFF AFTER
 DRAIN LINE TURNS TO MENS ROOM NOT REFLEC
 TED ON RISER DIAGRAM.
 7) GREASE TRAP SHALL BE SIZED BY RODNEY
 COMPO, ENVIRONMENTAL COMPLIANCE (561)
 837-4074. (SEE ATTACHED SHEET FOR APPRO-
 VED GREASE TRAP DETAIL)
 8) SHOWER BATH BY DANCE CLASS SHALL BE
 ACCESSIBLE PER FACBC-SEC 4.1.3(11)
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377