2002-04-05 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02020235 |
| 345 SUMMA ST |
| CONT: WHITING TURNER |
| TEL: 832-4995 |
| |
| SBC= 1997 STANDARD BUILDING CODE |
| SBC*= AMENDMENTS STANDARD BUILDING CODE |
| |
| 1) SBC 104.2.2* A RECENT SURVEY (LESS |
| THAN 1 YR. OLD) |
| 2) SBC 1804.2.7.1-2 SOILS TEST REQUIRED |
| TO DETERMINE THE MINIMUM SAFE BEARING |
| VALUE. |
| 3) THIS BUILDING WAS BROUGHT IN FOR PER- |
| MIT IN A TIME PERIOD (JAN- FEB 2002), |
| THE PLANS SHALL INDICATE UNDER WHAT |
| PARAMETERS & ASSUMPTIONS THIS PROJECT |
| WAS DESIGNED UNDER.1997 SBC OR 2001 FL |
| CODE.SHEET S-1.0 DESIGN CRITERIA, |
| WIND LOAD ASCE 7-98 WOULD INDICATE POSS- |
| IBLY THE 2001 FL CODE, UNDER THIS CODE |
| 1606.1.7 INDICATES THE REQUIREMENTS THAT |
| SHALL BE INDICATED ON THE DRAWINGS. |
| WIND SPEED: INDICATED ON PLANS AS 130, |
| UNDER THE SBC, THE WIND SPEED WAS 110MPH |
| WHILE THE 2001 FL CODE IT IS 140MPH. THE |
| PLAN INDICATES 130MPH? |
| 4)FLORIDA STATE STATUTE 553.71.(7) |
| THIS BUILDING QUALIFIES AAS A "THRESHOLD |
| BUILDING", ANY ASSEMBLY OCCUPAANCY WHICH |
| EXCEEDS 5,000 SQ FT AND AN OCCUPANT CON- |
| TENT OF GREATER THAN 500 PERSONS. |
| 5)DEPENDING IF THIS PLAN IS DESIGNED |
| UNDER THE 97 CODE OR 2001 FL CODE THE |
| ST STATUTE CHANGES BUT THE REQUIREMENT |
| FOR A THRESHOLD INSPECTION PLAN BE FILED |
| WITH THE BUILDING DEPARTMENT BY THE |
| ENGIEENER OF RECORD. THE THRESHOLD |
| COMPANY AND INSPECTOR SHALL MEET WITH |
| ASSISTANT BUILDING OFFICIAL DON NEELY |
| AS TO THE THRESHOLD INSPECTOR PROGRAM |
| WITHIN THE CITY CORP. LIMITS. |
| 6) PLANS AARE TO BE SUBMITTED TO COUNTY |
| FOR ASSESSMENT FOR IMPACT FEES, THEY |
| SHOULD BE EXEMPT ZERO DOLLARS DUE. |
| 7) CONTRACTOR TO PAY STATE RADON FEES |
| OF $177.50 TO CITY. |
| 8) SBC. 104.4.3* WHEN APPLICATION FOR |
| PEREMIT TO ERECT OR ENLARGE A BUILDING |
| HAS BEEN FILED AND PENDING ISSUANCE OF |
| SUCH PERMIT, THE BUILDING OFFICIAL MAY, |
| AT HIS/ HER DISCRETION ISSUE A SPECIAL |
| PERMIT FOR FOUNDATION ONLY. THE HOLDER |
| OF SUCH PERMIT IS PROCEEDING AT THEIR |
| OWN RISK AND WITHOUT ASSURANCE THAT A |
| PERMIT FOR THE REMAINDER OF THE WORK |
| WILL BE GRANTED NOR THAT CORRECTIONS |
| WILL NOT BE REQUIRED IN ORDER TO MEET |
| PROVISIONS OF THE TECHNICAL CODES. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X 8412 |
| THREE (3) SETS OF PLANS REQUIRED, |
| THRESHOLD BUILD!!!! |