Plan Review Notes
Plan Review Notes For Permit 02020235
Permit Number 02020235
Review Stop B
Sequence Number 2
Notes
Date Text
2002-04-05 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02020235
 345 SUMMA ST
 CONT: WHITING TURNER
 TEL: 832-4995
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 1) SBC 104.2.2* A RECENT SURVEY (LESS
 THAN 1 YR. OLD)
 2) SBC 1804.2.7.1-2 SOILS TEST REQUIRED
 TO DETERMINE THE MINIMUM SAFE BEARING
 VALUE.
 3) THIS BUILDING WAS BROUGHT IN FOR PER-
 MIT IN A TIME PERIOD (JAN- FEB 2002),
 THE PLANS SHALL INDICATE UNDER WHAT
 PARAMETERS & ASSUMPTIONS THIS PROJECT
 WAS DESIGNED UNDER.1997 SBC OR 2001 FL
 CODE.SHEET S-1.0 DESIGN CRITERIA,
 WIND LOAD ASCE 7-98 WOULD INDICATE POSS-
 IBLY THE 2001 FL CODE, UNDER THIS CODE
 1606.1.7 INDICATES THE REQUIREMENTS THAT
 SHALL BE INDICATED ON THE DRAWINGS.
 WIND SPEED: INDICATED ON PLANS AS 130,
 UNDER THE SBC, THE WIND SPEED WAS 110MPH
 WHILE THE 2001 FL CODE IT IS 140MPH. THE
 PLAN INDICATES 130MPH?
 4)FLORIDA STATE STATUTE 553.71.(7)
 THIS BUILDING QUALIFIES AAS A "THRESHOLD
 BUILDING", ANY ASSEMBLY OCCUPAANCY WHICH
 EXCEEDS 5,000 SQ FT AND AN OCCUPANT CON-
 TENT OF GREATER THAN 500 PERSONS.
 5)DEPENDING IF THIS PLAN IS DESIGNED
 UNDER THE 97 CODE OR 2001 FL CODE THE
 ST STATUTE CHANGES BUT THE REQUIREMENT
 FOR A THRESHOLD INSPECTION PLAN BE FILED
 WITH THE BUILDING DEPARTMENT BY THE
 ENGIEENER OF RECORD. THE THRESHOLD
 COMPANY AND INSPECTOR SHALL MEET WITH
 ASSISTANT BUILDING OFFICIAL DON NEELY
 AS TO THE THRESHOLD INSPECTOR PROGRAM
 WITHIN THE CITY CORP. LIMITS.
 6) PLANS AARE TO BE SUBMITTED TO COUNTY
 FOR ASSESSMENT FOR IMPACT FEES, THEY
 SHOULD BE EXEMPT ZERO DOLLARS DUE.
 7) CONTRACTOR TO PAY STATE RADON FEES
 OF $177.50 TO CITY.
 8) SBC. 104.4.3* WHEN APPLICATION FOR
 PEREMIT TO ERECT OR ENLARGE A BUILDING
 HAS BEEN FILED AND PENDING ISSUANCE OF
 SUCH PERMIT, THE BUILDING OFFICIAL MAY,
 AT HIS/ HER DISCRETION ISSUE A SPECIAL
 PERMIT FOR FOUNDATION ONLY. THE HOLDER
 OF SUCH PERMIT IS PROCEEDING AT THEIR
 OWN RISK AND WITHOUT ASSURANCE THAT A
 PERMIT FOR THE REMAINDER OF THE WORK
 WILL BE GRANTED NOR THAT CORRECTIONS
 WILL NOT BE REQUIRED IN ORDER TO MEET
 PROVISIONS OF THE TECHNICAL CODES.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412
 THREE (3) SETS OF PLANS REQUIRED,
 THRESHOLD BUILD!!!!