Plan Review Notes
Plan Review Notes For Permit 02020235
Permit Number 02020235
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-26 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) PLANS SHALL BE ROUTED TO THE PALM
 BEACH COUNTY HEALTH UNIT, DIVISION OF
 ENVIRONMENTAL HEALTH. 901 EVERNIA STREET
 WPB FLA 33401. THIS SHALL BE DONE BEFORE
 RESUBMITTING FOR PLAN REVIEW.
 2) PLEASE SUBMIT CALCULATIONS FOR MINI-
 MUM FACILITIES. USE SPC TABLE 407 AND
 SEC 407.1.3
 3) SHTS P-1/P-2 GREASE REISE DIA. DOES
 NOT REFLECT FLOOR PLAN. FLOOR PLAN SHOWS
 THREE FLOOR DRAINS TAKEN OFF FROM BLDG
 DRAIN. RISER DIAGRAM SHOWS ONE TAKEN OFF
 FROM BLDG DRAIN, AND ONE TAKEN OFF FROM
 BRANCH LINE AFTER 3 COMPARTMENT SINK.
 4) SHTS P-1/P-2 FLOOR SINK REQUIRED FOR
 INDIRECT WASTE FROM ICE MAKER. FLOOR
 DRAIN NOT APPROVED. SPC SEC 804.5
 5) SHTS P-1/P-2 JANITOR MOP SINK TO BE
 ON GREASE WASTE SYSTEM NOT SANITARY.
 6) SHTS P-1/P-2 ANY SINKS IN FOOD PREP
 AREA SHALL BE INDIRECT WASTE TO FLOOR
 SINK. SPC SEC 804.1
 7) SHTS P-1/P-2 SANITARY RISER DIAGRAM
 DOES NOT REFLECT FLOOR PLAN.
 A) SINK BEHIND HDCP LAV IN WOMENS REST
 ROOM ON RISER DIAGRAM NOT SHOWN ON FLOOR
 PLAN.
 B) DRINKING FOUNTAINS BY MENS AND WOMEN
 REST ROOMS ON FLOOR PLAN NOT SHOWN ON
 RISER DIAG.
 C) ARTS & CRAFTS TAKEN OFF BEFORE MENS
 ROOM ON FLOOR PLAN BUT NOT ON RISER DIA.
 D) CLEAN OUT AT CHANGE OF DIRECTION TO
 MENS ROOM MISSING ON RISER DIA.
 E) OFFICE BATH ROOM TAKEN OFF AFTER
 DRAIN LINE TURNS TO MENS ROOM NOT RE-
 FLECTED ON RISER DIA.
 F) FLOOR DRAIN BETWEEN URNAL AND W/C IN
 MENS ROOM SHOWN ON FLOOR PLAN NOT SHOWN
 ON RISER DIAGRAM.
 8) SHT ME-1 PLEASE SUBMIT STORM RISER
 DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377