2002-03-05 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| ---FOUNDATION PERMIT APPLICATION ONLY--- |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SHEET S-1.0, STRUCTURAL NOTES.THE |
| 'ALLOWABLE SOIL BEARING CAPACITY' IS |
| STATED AS 2500PSI.IF THIS WAS INTENDED |
| TO READ 2500PSF, AMEND THE PLANS |
| ACCORDINGLY. |
| |
| 3) SHEET S-2.0, FOUNDATION PLAN.THE |
| COLUMN ADJACENT TO THE MULTI-PURPOSE |
| ROOM DOOR LEADING TO THE ASSOCIATED |
| INNER ROOM (ASSUMED TO BE A STOREROOM) |
| IS LABELLED AS A TYPE 6 COLUMN.THIS |
| REFERENCE IS INCORRECT AS IT DOES NOT |
| CORRELATE TO TYPE 6 AS SHOWN ON THE |
| COLUMN SCHEDULE (SHEET S-1.0). |
| |
| 4) SHEET S-2.0, FOUNDATION PLAN.THE |
| COLUMN IN COMMENT (2) ABOVE, ALONG WITH |
| ONE OTHER, IS SHOWN AS BEING FOUNDED ON |
| ON A TYPE CF-405 FOOTING.THIS FOOTING |
| REFERENCE IS NOT INCLUDED IN THE FOOTING |
| SCHEDULE.AMEND THE PLAN OR SCHEDULE AS |
| APPROPRIATE. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |