Plan Review Notes
Plan Review Notes For Permit 02020196
Permit Number 02020196
Review Stop B
Sequence Number 4
Notes
Date Text
2002-07-11 00:00:00THIS PERMIT WILL BE ISSUED WITH A BUILD-
 ING PROVISO:
 1) THE ORIGINAL PLAN CHECK 1997 STANDARD
 BUILDING CODE.
 2) THE PERMIT APPLICATION AND HISTORY
 REFLECT THE ORIGINAL PLAN CHECK # NOT
 THE MARCH 8TH /2002 APPLIACTION DATE.
 A NEW PERMIT # SHALL BE ISSUED TO RE-
 FLECT THE APPLICATION BEING REVIEWED
 UNDER THE 2001 FLORIDA BUILDING CODE.
 3) THE SITE SPECIFIC ENGINEERING FOR THE
 DOOR, MULLIONS, SIDELIGHTS & TRANSOM
 ARE WIND ONLY.NEITHER THE DADE COUNTY
 PRODUCT APPROVAL REPORT# 01-0910.09
 NOR THE ENGINNEERING INDICATE THEY
 ARE TESTED FOR MORE THAN WIND.
 4) FL BLD CODE 1606.1.4/ 1707.4 &
 3401.7.2.4 REQUIRE GLAZED UNITS BEING
 REPLACED TO HAVE LARGE MISSLE IMPACT
 RESISTANCE TESTING OR STORM SHUTTER
 PROTECTION HAVING PASSED SUCH PRODUCT
 TESTING. EITHER SBCCI OR DADE COUNTY
 TESTING.
 5) THERE HAS BEEN NO SUCH REPORT SUBMIT-
 TED, A SEPARATE PERMIT SHALL BE
 REQUIRED FOR STORM SHUTTER BEFORE A
 CERTIFICATE OF COMPLETION SHALL BE
 ISSUED.
 6) A NEW PERMIT NUMBER SHALL BE ISSUED
 TO REFLECT THE PERMIT APP., REVIEWS
 AND HISTORY OF THIS PERMIT FOR TRACK-
 ING PURPOSES. PERMIT # 02070653.