2002-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT 02020196
 2825 OKEECHOBEE BLVD
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1) BUILDING INFORMATION, SHEET A0.0
 WRONG CODE USE,1997 STANDARD BUILDING
 CODEFOR BUILDING & 1994 STANDARD PLUMBI-
 ING CODE.
 2) PREVIOUS BUILDING REVIEW A PROVISO
 GIVEN FOR STOREFRONT PRODUCT APPROVAL.
 THE PRODUCT TESTING REPORT PROVIDED DOES
 NOT MEET THIS CONFIGURATION, UNDER LIMIT
 ATIOINS IT IS FOR A SINGLE OR DOUBLE SET
 OF DOORS ONLY. DETAIL 2 OF SHEET 2
 INDICATES 2 DOORS SIDELITES AS WELL AS
 A TRANSOM. THE REPORT ALSO STATES THAT
 HURRICANE PROTECTION SHALL BE REQUIRED.
 3) SHEET 4 INDICATES VARIOUS SOFFITS
 BUT NOWHERE DOES IT STATE HOW THE SOFFIT
 FRAMING IS ATTACHED? OR TO WHAT?
  
 4) PLANS SUBMITTED FOR PLAN REVIEW WERE
 UNDER THE 1997 STANDARD BUILDING CODE!
 **** PLANS SUBMITTED FOR PERMIT APPLICA-
 TION AFTER MARCH 1, 2002 TO BE DESIGNED
 TO THE 2001 FLORIDA BUILDING CODE!!!!!!
 ********2001 FLORIDA BUILDING CODE******
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412