Plan Review Notes For Permit 02020196 |
Permit Number |
02020196 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2002-03-30 00:00:00 | BUILDING PLAN REVIEW | | PERMIT 02020196 | | 2825 OKEECHOBEE BLVD | | | | SBC= 1997 STANDARD BUILDING CODE | | | | 1) BUILDING INFORMATION, SHEET A0.0 | | WRONG CODE USE,1997 STANDARD BUILDING | | CODEFOR BUILDING & 1994 STANDARD PLUMBI- | | ING CODE. | | 2) PREVIOUS BUILDING REVIEW A PROVISO | | GIVEN FOR STOREFRONT PRODUCT APPROVAL. | | THE PRODUCT TESTING REPORT PROVIDED DOES | | NOT MEET THIS CONFIGURATION, UNDER LIMIT | | ATIOINS IT IS FOR A SINGLE OR DOUBLE SET | | OF DOORS ONLY. DETAIL 2 OF SHEET 2 | | INDICATES 2 DOORS SIDELITES AS WELL AS | | A TRANSOM. THE REPORT ALSO STATES THAT | | HURRICANE PROTECTION SHALL BE REQUIRED. | | 3) SHEET 4 INDICATES VARIOUS SOFFITS | | BUT NOWHERE DOES IT STATE HOW THE SOFFIT | | FRAMING IS ATTACHED? OR TO WHAT? | | | | 4) PLANS SUBMITTED FOR PLAN REVIEW WERE | | UNDER THE 1997 STANDARD BUILDING CODE! | | **** PLANS SUBMITTED FOR PERMIT APPLICA- | | TION AFTER MARCH 1, 2002 TO BE DESIGNED | | TO THE 2001 FLORIDA BUILDING CODE!!!!!! | | ********2001 FLORIDA BUILDING CODE****** | | | | BUILDING PLAN REVIEW | | JIM WITMER | | (561) 659-8096 X 8412 |
|