Plan Review Notes
Plan Review Notes For Permit 02020196
Permit Number 02020196
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-02-07 00:00:001) WRONG LIFE SAFETY CODE REFERENCED
 IN BUILDING INFORMATION. SHOULD READ
 FLORIDA FIRE PREVENTION CODE, 2000
 EDITION OF THE LIFE SAFETY CODE.
 2) ARE THE 2X4 PARABOLIC WITH BATTERY
 BACKUP NIGHTLITES THE SAME AS EMERGENCY
 LIGHTS.
 3) GENERAL STORAGE AREAS AND CLOSETS
 ARE TO BE PROTECTED BY AT LEAST ONE
 HOUR FIRE RATED ASSEMBLIES WITH C
 LABELED OPENING PROTECTIVES.
 4) AREA SHOWN AS HATCHED ON THE PLANS
 IS USED FOR WHAT PURPOSE. IF USED FOR
 STORAGE IT MUST BE RATED BY AT LEAST
 ONE HOUR.
 5) IS THE DOOR IN THE HATCHED AREA
 LABELED AS AN EXIT.
 6) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910