Plan Review Notes For Permit 02020196 |
Permit Number |
02020196 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-07 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED | | IN BUILDING INFORMATION. SHOULD READ | | FLORIDA FIRE PREVENTION CODE, 2000 | | EDITION OF THE LIFE SAFETY CODE. | | 2) ARE THE 2X4 PARABOLIC WITH BATTERY | | BACKUP NIGHTLITES THE SAME AS EMERGENCY | | LIGHTS. | | 3) GENERAL STORAGE AREAS AND CLOSETS | | ARE TO BE PROTECTED BY AT LEAST ONE | | HOUR FIRE RATED ASSEMBLIES WITH C | | LABELED OPENING PROTECTIVES. | | 4) AREA SHOWN AS HATCHED ON THE PLANS | | IS USED FOR WHAT PURPOSE. IF USED FOR | | STORAGE IT MUST BE RATED BY AT LEAST | | ONE HOUR. | | 5) IS THE DOOR IN THE HATCHED AREA | | LABELED AS AN EXIT. | | 6) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION INFORMATION FOR WALLS | | AND CEILINGS. | | | | MIKE CARSILLO, CAPTAIN | | 659-8096,EXT.8497 | | 835-2910 |
|