2002-02-13 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 CODE REFERENCED ON A 0.0 IS INCORRECT,
 PLEASE NOTE WE ARE UNDER THE "99" NEC.
  
 2)NOTE: PLEASE NOTE MISSING SIGNAGE REQ`
 D PER 600-5.
  
 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62.
  
 4)NOTE: PLEASE SHOW TRACL LIGHTING CALCS
 PER 220-12B
  
 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR
 OUTLETS? PLEASE SHOW # OF OUTLETS AT
 180VA 220-3.
  
 6)NOTE: PLEASE SEE ANY FIRE PLAN REVIEW
 COMMENTS.
  
 PLEASE CLARIFY THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ANY QUESTIONS PLEASE
 CALL.
  