Plan Review Notes For Permit 02020196 |
Permit Number |
02020196 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-13 00:00:00 | *************** UNSAT ************** | | | | 1)NOTE: PLEASE NOTE THAT ELECTRICAL | | CODE REFERENCED ON A 0.0 IS INCORRECT, | | PLEASE NOTE WE ARE UNDER THE "99" NEC. | | | | 2)NOTE: PLEASE NOTE MISSING SIGNAGE REQ` | | D PER 600-5. | | | | 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW | | OUTLETS PER 210-62. | | | | 4)NOTE: PLEASE SHOW TRACL LIGHTING CALCS | | PER 220-12B | | | | 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR | | OUTLETS? PLEASE SHOW # OF OUTLETS AT | | 180VA 220-3. | | | | 6)NOTE: PLEASE SEE ANY FIRE PLAN REVIEW | | COMMENTS. | | | | PLEASE CLARIFY THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ANY QUESTIONS PLEASE | | CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|