Plan Review Notes
Plan Review Notes For Permit 02020149
Permit Number 02020149
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-11 00:00:00PLEASE PROVIDE THE FOLLOWING FOR
 ELECTRICAL REVIEW:
  
 1)LOAD CALCULATIONS OF THE PANEL FEEDING
 THE NEW A/C SYSTEM.
  
 2)DRAWING WITH CONDUIT & WIRE SIZE TO
 NEW UNITS.
  
 3)SHOW GFI AT CONDESING UNIT PER 309.2
 MECHANICAL CODE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096
 EXT 8392