Plan Review Notes For Permit 02020131 |
Permit Number |
02020131 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-08 00:00:00 | | | | | PLEASE CLARIFY THE FOLLOWING: | | | | 1.ACCESS FOR THE AHU. | | | | 2.RETURN AIR LOCATION. | | | | 3.BATHROOM EXHAUST...IS THERE ANY? | | | | 4.CONDENSATE LINE IS INDICATED AS 3/8" | | IS THIS THE LINE SIZE AT THE UNIT? | | AS PER 1997 SMC 304.8.4, CONDENSATE | | WASTE & DRAIN LINES SHALL BE NOT | | LESS THAN THE EQUIPMENT DRAIN LINE | | SIZE & IN NO CASE SHALL IT BE LESS | | THAN 3/4 PIPE OR 7/8 TUBING SIZE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|