Plan Review Notes
Plan Review Notes For Permit 02020131
Permit Number 02020131
Review Stop M
Sequence Number 1
Notes
Date Text
2002-02-08 00:00:00 
  
 PLEASE CLARIFY THE FOLLOWING:
  
 1.ACCESS FOR THE AHU.
  
 2.RETURN AIR LOCATION.
  
 3.BATHROOM EXHAUST...IS THERE ANY?
  
 4.CONDENSATE LINE IS INDICATED AS 3/8"
 IS THIS THE LINE SIZE AT THE UNIT?
 AS PER 1997 SMC 304.8.4, CONDENSATE
 WASTE & DRAIN LINES SHALL BE NOT
 LESS THAN THE EQUIPMENT DRAIN LINE
 SIZE & IN NO CASE SHALL IT BE LESS
 THAN 3/4 PIPE OR 7/8 TUBING SIZE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.