2002-02-14 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | 1) RISER DIAGRAM DOES NOT REFLECT FLOOR | | PLAN, AND NUMERIOUS FIXTURES ARE NOT | | VENTED PROPERLY. SOME FIXTURES ARE NOT | | ON RISER THAT ARE ON FLOOR PLAN AND SOME | | FIXTURES ON RISER DO NOT APPEAR ON FLOOR | | PLAN. PLEASE SHOW ALL PIPE SIZES ON 2ND | | FLOOR RISER DIAGRAM. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|