Plan Review Notes For Permit 02020084 |
Permit Number |
02020084 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-25 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | ALL NEW EQUIPMENT BEING INSTALLED. | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | CIRCUIT(S) PER 210-11-C-3. | | MUST BE 20A AND #12AWG. | | | | 3)NOTE: PLEASE NOTE THAT PLANS SHOW | | A GFI NEXT TO A/C COND AS OPT. PLEASE | | NOTE AN OUTLET IS REQ`D PER MECH CODE. | | 309.2 | | | | PLEASE SUBMIT THE ABOVEINFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 | | | | | | NOTE: PLEASE LIST THE REQ`D ARC FAULT | | PROTECTION PER 210-12 |
|