Plan Review Notes For Permit 02020084
Permit Number 02020084
Review Stop E
Sequence Number 1
Notes
Date Text
2002-02-25 00:00:00***************** UNSAT ****************
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3)NOTE: PLEASE NOTE THAT PLANS SHOW
 A GFI NEXT TO A/C COND AS OPT. PLEASE
 NOTE AN OUTLET IS REQ`D PER MECH CODE.
 309.2
  
 PLEASE SUBMIT THE ABOVEINFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
  
 NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12