Plan Review Notes
Plan Review Notes For Permit 02020068
Permit Number 02020068
Review Stop P
Sequence Number 1
Notes
Date Text
2002-02-12 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT A-2 EQUIPMENT SCHED. 21A LISTED
 BUT NOT FOUND ON FLOOR PLAN, PLEASE
 CLAIRFY.
 2) SHT A-2 EQUIP. SCHED. 34 WATER FILTER
 SHALL MEET NSF REQUIREMENTS. PLEASE FUR-
 NISH MANUFACTURE'S INFORMATION.
 3) SHT A-2 EQUIP. SCHED. 7 W/HEATER REQ-
 UIRES A PERMINATE SHIPS LADDER TO ASSURE
 READILY ACCESSIBLE. SHOW DETAILS.
 4) SHT A-3 WATER HEATER SUPPORT DETAIL,
 1/2" PAN DRAIN SHOWN. 1" MINIMUM DRAIN
 REQUIRED. SPC SEC 507.8.2
 5) SHT P-1 FLOOR PLAN WASTE & VENT, SEP-
 ARATE SANITARY AND GREASE LINES REQUIRED
 6) SHT P-1 GREASE TRAP CALCULATIONS.
 MINIMUM SIZE GREASE TRAP IS 750 GALS.
 GREASE TRAP TO BE SIZED BY ROD COMPO,
 ENVIRONMENTAL COMPLIANCE, (561) 837-4074
 WASTE ORD. #2938-96
 7) BACKFLOW REQUIRED ON WATER SERVICE
 SHALL BE MAX. 4' AFF FOR SERVICE. (SHT
 P-1 KEY NOTE #2).
 8) SHTS P-1/P-2 GREASE TRAP INSIDE BLDG.
 NOT APPROVED.
 9) SHT P-2 WASTE & VENT RISER DIAGRAM,
 3-COMPARTMENT SINK SHALL HAVE TRAPS ON
 EACH COMPARTMENT.
 10 SHT P-2 WATER RISER DIAGRAM, WATER
 FILTER NOT SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377