Plan Review Notes For Permit 02020068 |
Permit Number |
02020068 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-12 00:00:00 | DENIED | | REFERENCE: SPC-94-FACBC-97 | | | | 1) SHT A-2 EQUIPMENT SCHED. 21A LISTED | | BUT NOT FOUND ON FLOOR PLAN, PLEASE | | CLAIRFY. | | 2) SHT A-2 EQUIP. SCHED. 34 WATER FILTER | | SHALL MEET NSF REQUIREMENTS. PLEASE FUR- | | NISH MANUFACTURE'S INFORMATION. | | 3) SHT A-2 EQUIP. SCHED. 7 W/HEATER REQ- | | UIRES A PERMINATE SHIPS LADDER TO ASSURE | | READILY ACCESSIBLE. SHOW DETAILS. | | 4) SHT A-3 WATER HEATER SUPPORT DETAIL, | | 1/2" PAN DRAIN SHOWN. 1" MINIMUM DRAIN | | REQUIRED. SPC SEC 507.8.2 | | 5) SHT P-1 FLOOR PLAN WASTE & VENT, SEP- | | ARATE SANITARY AND GREASE LINES REQUIRED | | 6) SHT P-1 GREASE TRAP CALCULATIONS. | | MINIMUM SIZE GREASE TRAP IS 750 GALS. | | GREASE TRAP TO BE SIZED BY ROD COMPO, | | ENVIRONMENTAL COMPLIANCE, (561) 837-4074 | | WASTE ORD. #2938-96 | | 7) BACKFLOW REQUIRED ON WATER SERVICE | | SHALL BE MAX. 4' AFF FOR SERVICE. (SHT | | P-1 KEY NOTE #2). | | 8) SHTS P-1/P-2 GREASE TRAP INSIDE BLDG. | | NOT APPROVED. | | 9) SHT P-2 WASTE & VENT RISER DIAGRAM, | | 3-COMPARTMENT SINK SHALL HAVE TRAPS ON | | EACH COMPARTMENT. | | 10 SHT P-2 WATER RISER DIAGRAM, WATER | | FILTER NOT SHOWN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|