Plan Review Notes For Permit 02020068 |
Permit Number |
02020068 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2002-02-14 00:00:00 | *******************DENIED*************** | | | | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS AS | | PER ASHRAE 62-89. | | | | 2.CONDENSATE TO COMPLY WITH COUNTYWIDE | | AMENDMENTS 1994 SPC 804.3.(SHALL | | NOT TERMINATE INTO SANITARY). | | | | 3.OVERFLOW PROTECTION - AUXILIARY | | DRAIN LINE SHALL TERNIMATE AT A | | CONSPICUOUS POINT TO SERVE AS AN | | ALARM THAT REGULAR DRAIN IS | | RESTRICTED. | | | | SEPARATE PERMIT REQUIRED FOR ANY HOOD, | | FIRE SUPRESSION, AND WALK-IN | | COOLER/FREEZERS.PLEASE PROVIDE PLANS | | AND MANUFACTURER SUBMITTAL DATA WITH | | PERMIT APPLICATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|