Plan Review Notes
Plan Review Notes For Permit 02020023
Permit Number 02020023
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2002-02-14 00:00:001) FIRE ALARM CIRCUITS ARE TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 70,
 SECTION 760, NON POWER LIMITED FIRE
 ALARM CIRCUITS.
 2) FIRE ALARM AND FIRE SPRINKLER SYSTEM
 TO BE MONITORED BY A LICENSED UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910