Plan Review Notes For Permit 02011628 |
Permit Number |
02011628 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2002-05-24 00:00:00 | DENIED | | REFERENCE: SPC-94 - FACBC-97 | | | | 1) SHT MP-2 WATER RISER DIAGRAM - WATER | | HAMMER ARRESTORS SHALL BE LOCATED NEAR | | FIXTURES IN AN "EFFECTIVE RANGE" -NOT- | | AT TOP OF DROPS AS SHOWN. PLEASE CHANGE | | PLANS | | 2) SHT A-1 DRINKING FOUNTAINS SHALL | | COMPLY WITH SEC 4.15. PLEASE PROVIDE | | DETAILS WITH 4.25.2 SPOUT HEIGHT, 4.15.5 | | CLEAR FLOOR SPACE, & 4.1.3(10) PROVIDE | | FOR THOSE WHO HAVE DIFFICULTY BENDING OR | | STOOPING. (HI/LOW D.F OR CUP DISPENSER) | | 3) SHT A-1 STORAGE AREAS SHALL HAVE ONE | | EACH MALE AND FEMALE TOILET R00MS FOR | | EACH FLOOR PER OCCUPANT LOAD GIVEN. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT 8377 |
|