Plan Review Notes
Plan Review Notes For Permit 02011628
Permit Number 02011628
Review Stop P
Sequence Number 3
Notes
Date Text
2002-05-24 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT MP-2 WATER RISER DIAGRAM - WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 FIXTURES IN AN "EFFECTIVE RANGE" -NOT-
 AT TOP OF DROPS AS SHOWN. PLEASE CHANGE
 PLANS
 2) SHT A-1 DRINKING FOUNTAINS SHALL
 COMPLY WITH SEC 4.15. PLEASE PROVIDE
 DETAILS WITH 4.25.2 SPOUT HEIGHT, 4.15.5
 CLEAR FLOOR SPACE, & 4.1.3(10) PROVIDE
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING. (HI/LOW D.F OR CUP DISPENSER)
 3) SHT A-1 STORAGE AREAS SHALL HAVE ONE
 EACH MALE AND FEMALE TOILET R00MS FOR
 EACH FLOOR PER OCCUPANT LOAD GIVEN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377