Plan Review Notes
Plan Review Notes For Permit 02011628
Permit Number 02011628
Review Stop E
Sequence Number 2
Notes
Date Text
2002-03-25 00:00:00****************** UNSAT ***************
  
 PLEASE NOTE THAT NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SHOW LOAD CALCAULTIONS,
 NOTHING SHOWN. PLEASE NOTE ALL CONTINUOS
 LOADS NEED TO BE SHOWN AT 125%. 215-3,
 230-42 ETC.
  
 2)NOTE: PLEASE NOTE THAT UNIT "A" SHOWS
 PANEL "H" BEING INSIDE UNIT? PLEASE
 CLARIFY IF THIS IS "HOUSE" PANEL AND
 WHY IT IS SHOWN IN UNIT"A". GROUPING
 MAINS.230-72
 3)NOTE: PLEASE NOTE THAT PANEL"S" THAT
 IS SHOWN FOR STORAGE AREA DOES NOT
 CORRELATE ON RISER DIAGRAM. PLEASE NOTE
 OTHER METER LOCATION MENTIONS FOR FIRST
 FLOOR STORAGE? ARE THESE FOR POSSIBLE
 FUTURE TENANT SPACE?
 PLEASE NOTE THAT RISER MENTIONS THAT
 THERE WILL BE "MCB" PANELS IN THOSE
 AREAS, PLEASE NOTE GROUPING OF MAINS
 ON PLANS. 230-72
  
 4)NOTE: PLEASE CLARIFY "NUMBER OF
 SERVICE DROPS" AS NOTED ON PLANS> PLEASE
 NOTE THAT ONLY ONE SERVICE DROP IS
 PERMITTED UNDER 230-70. PLEASE CLARIFY
 IF THIS NOTE IS MEANT FOR "3" SETS OF
 SERVICE ENTRANCE CONDUCTORS.?
  
 5)NOTE: PLEASE NOTE THAT MAIN DISCONNECT
 FOR PANEL "S" IS SHOWN AS 200A WITH
 150A OCP. PLEASE NOTE THAT CONDUCTORS
 TO PANEL ARE ONLY SHOWN AS #6`S??
 310-16.
  
 6)NOTE: PLEASE NOTE THAT SERVICE
 ENTRANCE CONDUCTORS ARE SHOWN AS 3 SETS
 OF 500MCM. PLEASE NOTE PER 310-16/110-14
 500MCM IS RATED AT 380A. PLEASE NOTE
 240-3-C. RATED FOR MAIN.
  
 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP-
 -MENT GROUNDING BETWEEN MAINS AND PANELS
 . SIZE PER 250-122
  
 8)NOTE: PLEASE NOTE MISSING MAIN FOR
 PANEL"A". 230-72.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372