2002-03-25 00:00:00 | ****************** UNSAT *************** |
| |
| PLEASE NOTE THAT NOT ALL NOTES FROM |
| FIRST REVIEW WERE ADDRESSED. |
| |
| 1)NOTE: PLEASE SHOW LOAD CALCAULTIONS, |
| NOTHING SHOWN. PLEASE NOTE ALL CONTINUOS |
| LOADS NEED TO BE SHOWN AT 125%. 215-3, |
| 230-42 ETC. |
| |
| 2)NOTE: PLEASE NOTE THAT UNIT "A" SHOWS |
| PANEL "H" BEING INSIDE UNIT? PLEASE |
| CLARIFY IF THIS IS "HOUSE" PANEL AND |
| WHY IT IS SHOWN IN UNIT"A". GROUPING |
| MAINS.230-72 |
| 3)NOTE: PLEASE NOTE THAT PANEL"S" THAT |
| IS SHOWN FOR STORAGE AREA DOES NOT |
| CORRELATE ON RISER DIAGRAM. PLEASE NOTE |
| OTHER METER LOCATION MENTIONS FOR FIRST |
| FLOOR STORAGE? ARE THESE FOR POSSIBLE |
| FUTURE TENANT SPACE? |
| PLEASE NOTE THAT RISER MENTIONS THAT |
| THERE WILL BE "MCB" PANELS IN THOSE |
| AREAS, PLEASE NOTE GROUPING OF MAINS |
| ON PLANS. 230-72 |
| |
| 4)NOTE: PLEASE CLARIFY "NUMBER OF |
| SERVICE DROPS" AS NOTED ON PLANS> PLEASE |
| NOTE THAT ONLY ONE SERVICE DROP IS |
| PERMITTED UNDER 230-70. PLEASE CLARIFY |
| IF THIS NOTE IS MEANT FOR "3" SETS OF |
| SERVICE ENTRANCE CONDUCTORS.? |
| |
| 5)NOTE: PLEASE NOTE THAT MAIN DISCONNECT |
| FOR PANEL "S" IS SHOWN AS 200A WITH |
| 150A OCP. PLEASE NOTE THAT CONDUCTORS |
| TO PANEL ARE ONLY SHOWN AS #6`S?? |
| 310-16. |
| |
| 6)NOTE: PLEASE NOTE THAT SERVICE |
| ENTRANCE CONDUCTORS ARE SHOWN AS 3 SETS |
| OF 500MCM. PLEASE NOTE PER 310-16/110-14 |
| 500MCM IS RATED AT 380A. PLEASE NOTE |
| 240-3-C. RATED FOR MAIN. |
| |
| 7)NOTE: PLEASE CLARIFY MEANS OF EQUIP- |
| -MENT GROUNDING BETWEEN MAINS AND PANELS |
| . SIZE PER 250-122 |
| |
| 8)NOTE: PLEASE NOTE MISSING MAIN FOR |
| PANEL"A". 230-72. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |