2002-03-26 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02011628
 1609 S DIXIE
 CONT: MIKE MOORE CONST
 TEL: 775-3447
  
 SBC= 1997STANDARD BUILDING CODE
 FL ACC CODE= FLORIDA ACCESSIBILITY CODE
  
 1)- SBC1606.4 PRODUCT APPROVALS SHEET
 A-2 INDICATES THE REMOVAL OF THE EXIST-
 ING STOREFRONT. 2 COPIES EITHER DADE
 COUNTY OR SBCCI REPORT.
 2)- SBC2405 GLAZING IN HAZARDOUS LOCA-
 TIONS. NEW STOREFRONT DOORS 100A,300A,
 AND 400A.
 3)- SBC 704.1 HAZARD H-2 LOW HAZARD,
 WHAT TYPE OF MATERIALS TO BE SSTORED?
 A 2 HR FLOOR CEILING RATING SHALL BE
 REQUIRED BETWEEN MERCANTILE / STORAGE.
 SHOW FLOOR/ CEILING UL RATING.
 4) STORAGE SECOND FLOOR REQUIRES 2
 MEANS OF EGRESS 1027.1.1.
 5)- SBC AMEND. 106.4 POSTING OF FLOOR
 LOADS 106.4.2 IT SHALL BE THE OWNER,
 AGENT OF GROUP S AND F OCCUPANCIES TO EM
 PLOY A COMPUTANT ARCHETECT OR ENGINEER
 TO COMPUTE THE SAFE FLOOR ALLOWABLE
 FLOOR LOADING CAPACITY. ALL SUCH COMPUTA
 TIONS SHALL BE ACCOMPANIED BY AN AFFIDAV
 IT FROM THE DESIGN PROFESSIONAL STATING
 THE SAFE FLOOR LOAD. THE COMPUTATIONS &
 AFFIDAVIT SHALL BE ON FILE AS A PERMAN-
 ENT RECORD OF THE BUILDING DEPARTMENT.
 SBC 106.4.3 SIGNS REQUIRED OWNERS RESPON
 CIBILITY TO ENSURE THAT THE SAFE FLOOR
 LOADS SHALL BE.
 6)- SBC TABLE 1604.1 WHAT IS THE SECOND
 FLOOR DESIGNED TO FOR LIVE LOADS?
 7) - THE FIRST FLOOR COORIDORS, 500 &
 600, WHERE DOES THE FLOOR CEILING RATING
 OCCUR AROUND THE FLOORESCENT CEILING
 FIXTURES?
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412