2002-03-26 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT # 02011628 |
| 1609 S DIXIE |
| CONT: MIKE MOORE CONST |
| TEL: 775-3447 |
| |
| SBC= 1997STANDARD BUILDING CODE |
| FL ACC CODE= FLORIDA ACCESSIBILITY CODE |
| |
| 1)- SBC1606.4 PRODUCT APPROVALS SHEET |
| A-2 INDICATES THE REMOVAL OF THE EXIST- |
| ING STOREFRONT. 2 COPIES EITHER DADE |
| COUNTY OR SBCCI REPORT. |
| 2)- SBC2405 GLAZING IN HAZARDOUS LOCA- |
| TIONS. NEW STOREFRONT DOORS 100A,300A, |
| AND 400A. |
| 3)- SBC 704.1 HAZARD H-2 LOW HAZARD, |
| WHAT TYPE OF MATERIALS TO BE SSTORED? |
| A 2 HR FLOOR CEILING RATING SHALL BE |
| REQUIRED BETWEEN MERCANTILE / STORAGE. |
| SHOW FLOOR/ CEILING UL RATING. |
| 4) STORAGE SECOND FLOOR REQUIRES 2 |
| MEANS OF EGRESS 1027.1.1. |
| 5)- SBC AMEND. 106.4 POSTING OF FLOOR |
| LOADS 106.4.2 IT SHALL BE THE OWNER, |
| AGENT OF GROUP S AND F OCCUPANCIES TO EM |
| PLOY A COMPUTANT ARCHETECT OR ENGINEER |
| TO COMPUTE THE SAFE FLOOR ALLOWABLE |
| FLOOR LOADING CAPACITY. ALL SUCH COMPUTA |
| TIONS SHALL BE ACCOMPANIED BY AN AFFIDAV |
| IT FROM THE DESIGN PROFESSIONAL STATING |
| THE SAFE FLOOR LOAD. THE COMPUTATIONS & |
| AFFIDAVIT SHALL BE ON FILE AS A PERMAN- |
| ENT RECORD OF THE BUILDING DEPARTMENT. |
| SBC 106.4.3 SIGNS REQUIRED OWNERS RESPON |
| CIBILITY TO ENSURE THAT THE SAFE FLOOR |
| LOADS SHALL BE. |
| 6)- SBC TABLE 1604.1 WHAT IS THE SECOND |
| FLOOR DESIGNED TO FOR LIVE LOADS? |
| 7) - THE FIRST FLOOR COORIDORS, 500 & |
| 600, WHERE DOES THE FLOOR CEILING RATING |
| OCCUR AROUND THE FLOORESCENT CEILING |
| FIXTURES? |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| (561)659-8096 X 8412 |