2002-02-06 00:00:00 | ***************** UNSAT ************ |
| |
| 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING |
| NEEDS TO BE SHOWN ON PLANS AND CORRELATE |
| WITH A PANEL SCHEDULE. |
| |
| 2)NOTE: PLEASE NOTE THAT PLANS NEED TO |
| BE COMPLETE FOR STORAGE AREA AND SECOND |
| FLOOR. |
| |
| 3)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS |
| AND NOTE THAT "GARAGE" STORAGE NEEDS TO |
| BE CLARIFIED. |
| |
| 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS |
| WERE SUBMITTED.215-5 |
| |
| 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM |
| SHOWS 3-#10`S TO 150A PANEL? MISPRINT? |
| |
| 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110-9. |
| |
| 7)NOTE: PLEASE NOTE THAT NO GROUNDING |
| ELECTRODE SYSTEM IS SHOWN.215-5/250 |
| |
| 8)NOTE: PLEASE CLARIFY MAINS NOT SHOWN |
| FOR FIRST FLOOR AND SECOND FLOOR STORAGE |
| AREAS.?? PANELS? PLEASE NOTE GROUPING |
| OF MAINS PER 230-72. |
| |
| 9)NOTE: PLEASE NOTE THAT FIRST FLOOR |
| STORAGE SHOWS ELECTRICAL BUT NO PANEL |
| |
| 10)NOTE: PLEASE NOTE MISSING SHOW WINDOW |
| OUTLETS PER 210-62 |
| |
| 11)NOTE: PLEASE NOTE MISSING SIGN PER |
| 600-5. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |