2002-02-06 00:00:00***************** UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT ALL CIRCUITING
 NEEDS TO BE SHOWN ON PLANS AND CORRELATE
 WITH A PANEL SCHEDULE.
  
 2)NOTE: PLEASE NOTE THAT PLANS NEED TO
 BE COMPLETE FOR STORAGE AREA AND SECOND
 FLOOR.
  
 3)NOTE: PLEASE NOTE FIRE REVIEW COMMENTS
 AND NOTE THAT "GARAGE" STORAGE NEEDS TO
 BE CLARIFIED.
  
 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS
 WERE SUBMITTED.215-5
  
 5)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS 3-#10`S TO 150A PANEL? MISPRINT?
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7)NOTE: PLEASE NOTE THAT NO GROUNDING
 ELECTRODE SYSTEM IS SHOWN.215-5/250
  
 8)NOTE: PLEASE CLARIFY MAINS NOT SHOWN
 FOR FIRST FLOOR AND SECOND FLOOR STORAGE
 AREAS.?? PANELS? PLEASE NOTE GROUPING
 OF MAINS PER 230-72.
  
 9)NOTE: PLEASE NOTE THAT FIRST FLOOR
 STORAGE SHOWS ELECTRICAL BUT NO PANEL
  
 10)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLETS PER 210-62
  
 11)NOTE: PLEASE NOTE MISSING SIGN PER
 600-5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372