Plan Review Notes
Plan Review Notes For Permit 02011628
Permit Number 02011628
Review Stop B
Sequence Number 1
Notes
Date Text
2002-02-13 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) UNTIL MARCH 1, 2001 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE WHICH
 CODE THE WORK IS TO BE CONSTRUCTED TO.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SBC* 1606.4 (FBC 1606.1.4)PRODUCT
 APPROVALS.SUBMIT PRODUCT APPROVALS FOR
 THE NEW STOREFRONTS AND EXTERIOR GLAZED
 DOORS 100A, 200A, 300A AND 400A ON
 S. DIXIE HWY, AND FOR THE NEW STOREFRONT
 LITES ON THE PALM STREET ELEVATION.
  
 4) SBC 2405 (FBC 2405)GLAZING IN
 HAZARDOUS LOCATIONS.ANNOTATE THE DOOR
 SCHEDULE TO SHOW THE REQUIREMENT FOR
 TEMPERED, OR ALTERNATIVE SAFETY, GLAZING
 IN DOORS 100A, 200A, 300A AND 400A.
  
 5) FL ACC CODE 4.22 (FBC 11-4.22)
 SHEET A-1, FLOOR PLAN.THE 'TYPICAL
 TOILET ROOM' ELEVATIONS DO NOT SHOW
 SUFFICIENT DIMENSIONS TO ENSURE
 COMPLIANCE WITH FIGURE 29, FOR EXAMPLE,
 DISTANCE BETWEEN THE W.C. AND ADJACENT
 WALL.ALSO, DOOR 401 IS NOT INCLUDED ON
 THE DOOR SCHEDULE.
  
 6) FL ACC CODE 4.15 (FBC 11-4.15)AN
 ACCESSIBLE DRINKING FOUNTAIN, IN
 COMPLIANCE WITH FIGURE 27, SHALL BE
 PROVIDED IN EACH TENANT SPACE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499