2002-02-13 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 659 8096 EXT 8499 |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| SBC = STANDARD BUILDING CODE 1997 |
| SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| FL ACC CODE = FLORIDA ACCESSIBILITY CODE |
| |
| 1) UNTIL MARCH 1, 2001 EITHER STANDARD |
| BUILDING CODE 1997 OR FLORIDA BUILDING |
| CODE 2001 MAY BE USED.NEITHER CODE IS |
| REFERENCED ON THE PLANS.STATE WHICH |
| CODE THE WORK IS TO BE CONSTRUCTED TO. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SBC* 1606.4 (FBC 1606.1.4)PRODUCT |
| APPROVALS.SUBMIT PRODUCT APPROVALS FOR |
| THE NEW STOREFRONTS AND EXTERIOR GLAZED |
| DOORS 100A, 200A, 300A AND 400A ON |
| S. DIXIE HWY, AND FOR THE NEW STOREFRONT |
| LITES ON THE PALM STREET ELEVATION. |
| |
| 4) SBC 2405 (FBC 2405)GLAZING IN |
| HAZARDOUS LOCATIONS.ANNOTATE THE DOOR |
| SCHEDULE TO SHOW THE REQUIREMENT FOR |
| TEMPERED, OR ALTERNATIVE SAFETY, GLAZING |
| IN DOORS 100A, 200A, 300A AND 400A. |
| |
| 5) FL ACC CODE 4.22 (FBC 11-4.22) |
| SHEET A-1, FLOOR PLAN.THE 'TYPICAL |
| TOILET ROOM' ELEVATIONS DO NOT SHOW |
| SUFFICIENT DIMENSIONS TO ENSURE |
| COMPLIANCE WITH FIGURE 29, FOR EXAMPLE, |
| DISTANCE BETWEEN THE W.C. AND ADJACENT |
| WALL.ALSO, DOOR 401 IS NOT INCLUDED ON |
| THE DOOR SCHEDULE. |
| |
| 6) FL ACC CODE 4.15 (FBC 11-4.15)AN |
| ACCESSIBLE DRINKING FOUNTAIN, IN |
| COMPLIANCE WITH FIGURE 27, SHALL BE |
| PROVIDED IN EACH TENANT SPACE. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| IF YOU HAVE ANY QUERIES PLEASE CALL: |
| ROBERT BROWN(561) 659 8096 EXT 8499 |