Plan Review Notes
Plan Review Notes For Permit 02011614
Permit Number 02011614
Review Stop R
Sequence Number 4
Notes
Date Text
2002-05-28 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/12/02:
  
 1) RESPONSE LETTER OF 4/22/02 IS NOTED.
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) RESPONSE LETTER OF 4/22/02 IS NOTED.
 IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY, THE PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) FBC* 104.2.4SITE SURVEY.CONTRARY
 TO THE LETTER OF RESPONSE DATED 4/22/02,
 THE SIGNED AND SEALED SURVEY DRAWING WAS
 NOT SUBMITTED.
  
 4) RESPONSE LETTER OF 4/22/02 IS NOTED.
 FBC* 104.2.1.1ROOF COVERING PRODUCT
 APPROVAL SHALL BE SUBMITTED FOR THE ROOF
 COVERING SYSTEM TO BE USED (FBC 1504.3)
  
 5) FBC* 1804.2.2THE GEOTECHNICAL
 REPORT WAS SUBMITTED AS REQUIRED, BUT
 THE FOUNDATION/STRUCTURAL PLANS WERE NOT
 RESUBMITTED FOR CORRELATION CHECKS TO BE
 CARRIED OUT.RESUBMIT ALL DOCUMENTS.
  
 7) RESPONSE LETTER OF 4/22/02 IS NOTED.
 FBC 1606.1.4WINDOW AND DOOR PRODUCT
 APPROVALS.SUBMIT PRODUCT APPROVALS FOR
 THE EXTERIOR DOOR AND WINDOW SYSTEMS TO
 BE USED.
  
 9) FBC 13-103THREE COPIES OF THE HVAC
 LOAD ANALYSIS WERE RECEIVED BUT
 COMPLIANCE MUST BE DEMONSTRATED BY
 SUBMITTAL OF APPROPRIATE ENERGY CODE
 COMPLIANCE FORMS.
  
 11) FBC 1019.1.1 EXIT FROM ASSEMBLY RMS
 SHEET LS-105, SECOND FLOOR.THE LETTER
 OF RESPONSE DATED 4/22/02 IS NOTED.ADD
 PAINTED STRIPES WITH WARNING: FIRE
 EGRESS KEEP CLEAR, BETWEEN DOOR G22 AND
 THE STEPS/RAMP, ON SHEETS LS-103 & A-103
  
 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED'
 ROOM, SHEET LS-106.IF THE EGRESS
 CAPACITY HAS BEEN CALCULATED BASED ON
 OFFICE USE AS STATED, THEN CHANGE THE
 ROOM NAME FROM 'UNASSIGNED' TO 'OFFICE'.
  
 17) FROM THE LETTER OF RESPONSE, IT IS
 NOTED THAT STAIR #3 IS NOT AN EXIT. WITH
 REFERENCE TO SHEET LS-106, THE COMMON
 PATH OF TRAVEL (FBC 202 & 1020.6) FROM
 COMMUNITY CONFERENCE ROOM (3-003) AND
 THE RECEPTION (3-002) MAY EXCEED 100 FT.
 SHOW THE PROPOSED FURNITURE IN THESE
 ROOMS ON THE LIFE SAFETY PLAN AND SHOW
 THAT THE COMMON PATH OF TRAVEL TO THE
 NORTH SECTION OF CORRIDOR 3-010 DOES NOT
 EXCEED 100 FT.ALTERNATIVELY, AMEND THE
 EGRESS SIGNS AND DOOR LOCKS TO PROVIDE A
 SECOND EGRESS PATH VIA CORRIDOR 3-024.
  
 21) FBC 104.2.1EXTERIOR ALUMINUM
 CLADDING PANELS.THIS COMMENT HAS NOT
 BEEN PROPERLY ADDRESSED.THE REVISION
 TO DETAIL 8/A-705 DOES NOT SHOW THE
 MEANS OF ATTACHING THE ALUMINUM-FACED
 PLYWOOD PANELS TO THE BUILDING FACADE.
  
 23)
2002-05-22 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 PARADISE BAY-MASTER MODEL A
  
 --PROVISO--
 HURRICANE MISSILE IMPACT PROTECTION
 SHUTTERS.THE ROBICO SHUTTERS INC.
 DRAWINGS SUBMITTED DO NOT FORM PART OF A
 PRODUCT APPROVAL.SUBMIT A PRODUCT
 APPROVAL NOTICE OF ACCEPTANCE WITH
 ASSOCIATED DRAWINGS FOR THE PROPOSED
 SHUTTERS.