Plan Review Notes For Permit 02011614 |
Permit Number |
02011614 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2002-05-20 00:00:00 | PROVISO: | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | PER 2001 FBC 1503.4.4. | | | | MINIMUM OF 10 FT SEPARATION BETWEEN | | DRYER EXHAUST & O.A. INTAKE. | | | | EXHAUST & INTAKE OPENINGS SHALL BE | | LOCATED A MINIMUM OF 10 FT FROM LOT | | LINES OR BUILDINGS ON THE SAME LOT. | | 2001 FBC(M) 401.5. | | | | BALANCING DAMPERS OR OTHER MEANS OF | | SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED | | IN THE BRANCH DUCTS OR AT EACH | | INDIVIDUAL DUCT REGISTER, GRILLE OR | | DIFFUSER. 2001 FBC(M) 603.15 | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT 659-8096 | | EXT. 8388. |
|